PDRP-1002 Instruction Manual PN 51135:B0 04/06/01 7
1. Product Description

Overview

The PDRP-1002 Agent Release Control System has been designed as a control center for use in automatic
fire supression systems. The panel is a feature-packed control unit suitable to perform detection and control
functions associated with the release of gaseous agent/special hazard fire protection systems. The PDRP-
1002 is designed for maximum reliability with 100% solid state circuitry and isolated relay contacts for
outside interfacing and features programmable options to allow on-site customization of the unit for various
operating configurations.
An integral standby battery system, with charger, is provided. In case of commercial AC power
interruption, automatic switchover to the battery system will provide power to the panel for a minimum
of 24 hours.
The FACP is supplied complete with backbox, hinged door, control switches, and indicator LEDs.
The entire unit is housed in a standard sheet-metal enclosure with 1/2 in. (12.7 mm) and 3/4 in. (19.05 mm)
conduit knockouts available.
The PDRP-1002 is a 110/120 VAC agent release control panel. The PDRP-1002E is a 220/240 VAC agent
release control panel.

Features

Options

Note: Applications which require the 411UDAC or the NOTI-FIRE 911AC are not FM approved.
• Microprocessor-controlled
Power-limited on all circuits except Municipal Box
Output and Releasing Circuits
Alarm and trouble resound
Four Style B/D Initiating Device Circuits
Two Style Y/Z Notification Appliance Circuits
Two Style Y only Release Circuits
General alarm and trouble relays
Delay Timer (adjustable)
Three abort function options
Abort and manual release circuits
Designed for supression standards
Disable/enable controls per Initiating Device Circuit
Last Event Recall
Battery /Earth fault supervision
Current protection on all notification circuits
RMS regulated output power, 2.25 amps
7 amp-hour (AH) to 18 AH battery options, up to 90
hours standby
Resettable and nonresettable regulated power
outputs
Extensive transient protection
Watchdog timer to supervise microprocessor
Output circuits protected against false activations
Slide-in zone identification labels
Steel cabinet 14.5” (36.83cm) wide by 16.00”
(40.64cm) high by 4.75” (12.07cm) deep
4XZM Module for 4 zone/function relays
4XTM Transmitter Module - Complies with NFPA
72 Auxiliary and Remote Station Protective
Signaling systems
4XMM Volt/Amp Meter Module
RZA-4X Supervised remote annunciator (requires
4XLM Interface Module)
411UDAC or NOTI•FIRE 911AC Digital
Communicator - Complies with NFPA 72 Central
Station and Remote Station Protective Signaling
systems
Cross-zone option
Supervisory Input option
Dead-front dress panel option (DP-4X) (Required
for Canadian applications)
Trim ring for flush mount between 16 in. (40.64 cm)
center studs (TR-4XR)