System Sensor S1224MC specifications Installation And Maintenance Instructions, Specifications

Models: S1224MC

1 4
Download 4 pages 4.19 Kb
Page 1
Image 1
INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION AND MAINTENANCE INSTRUCTIONS

SpectrAlert Selectable Output Strobes, Horns, and Horn/Strobes

For use with the following models:

Strobes - 12/24 volt: S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW

Combo - 12/24 volt: P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, P1224MCPW Horns - H12/24, H12/24W

3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com

Suffix “W” indicates white housing models. Suffix “SP” indicates “FUEGO” (Spanish word for “FIRE”) lettering on housing. Suffix “P” indicates plain housing (no lettering).

The Products to which this manual applies may be covered by one or more of the

following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,133,843; 6,522,261; 6,661,337; 5,931,569; 6,793,375; 6,822,400; 6,833,783; 6,838,997

Specifications

Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified)

Electrical

 

Horns, Strobes, and

 

Horn/Strobes Voltages:

Regulated 12 DC/FWR and Regulated 24 DC/FWR

Operational Voltage Ranges:

12V=8-17.5 Volts; 24V=16-33 Volts

Synchronous Applications

 

with MDL Module:

12V=9-17.5 Volts; 24V=17-33 Volts

Operational Humidity Range:

10-93% RH (non-condensing)

NOTE: Horn units will operate on walk tests with on-time durations of .25 sec. or greater.

Flash Rate:

1 flash per second

Operating Temperature:

32° F to 120° F (0° C to 49° C)

Selectable Light Outputs:

All candelas are selectable via a manual slide switch.

12/24 Volt Applications:

15 or 15/75 candela

24 Volt Application:

30, 75, 110 candela

 

15/75 is listed at 15 candela per UL 1971 but will provide 75 candela on axis

 

(straight ahead). 15, 30, 75, or 110 are rated for that candela.

Sound Output:

Sound output levels are established at Underwriters Laboratories in their reverber-

 

ant room. Always use the sound output specified as UL Reverberant Room when

 

comparing products.

Listings:

UL S5512 (Strobe); UL S4011 (Combo)

Note for Strobes:

Do not exceed: 1) 8-17.5 or 16-33 voltage range limit; 2) maximum number of 70

 

strobe lights when connecting the MDL Sync module with a maximum line im-

 

pedance of 4 ohms per loop and; 3) maximum line impedance as required by the

 

fire alarm control manufacturer.

The models S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW, P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, and P1224MCPW incorporate a patented voltage booster design that has a more consistent flash bulb voltage over the range of candela selections. The benefit to the customer is a high quality strobe device.

General Description

The SpectrAlert series notification appliances are designed to meet the requirements of most agencies governing these devices, including: NFPA, ADA, The National Fire Alarm Code, UL, ULC, FM, CSFM, MEA. Also, check with your local Authority Having Jurisdiction for other codes or standards that may apply.

The SpectrAlert series can be installed in systems using 12- or 24- volt panels having DC or full-wave rectified (FWR) power supplies. The series can also be installed in systems requiring synchroniza- tion (module MDL or compatible equivalent required) or systems that do not require synchronization (no module required).

NOTICE: This manual shall be left with the owner/user of this equipment.

Fire Alarm System Considerations

Temporal and Non-Temporal Coded Signals:

The American National Standards Institute and the National Fire Alarm Code require that all horns used for building evacuation in-

stalled after July 1, 1996, must produce Temporal Coded Signals.

Signals other than those used for evacuation purposes do not have to produce the Temporal Coded Signal. Temporal coding is accom- plished by interrupting a steady sound in the following manner:

1/2 Sec.

1/2 Sec.

1/2 Sec.

1/2 Sec.

1/2 Sec.

11/2 Sec.

Repeats

On

Off

On

Off

On

Off

 

Power Supply Considerations

Panels typically supply DC filtered voltage or FWR (full-wave rectified) voltage. The system design engineer must calculate the number of units used in a zone based on the type of panel supply. Be certain the sum of all the device currents do not exceed the current capability of the panel. Calculations are based on using the device current found in the subsequent charts and must be the current specified for the type of panel power supply used.

D900-28-00

1

I56-1796-011R

Page 1
Image 1
System Sensor S1224MC specifications Installation And Maintenance Instructions, Specifications, Electrical