Technicolor - Thomson EAP 110 manual Specifications, Ordering Information, External Connections

Models: EAP 110

1 2
Download 2 pages 28.08 Kb
Page 2
Image 2
SPECIFICATIONS

SPECIFICATIONS

SUPPLY VOLTAGE

12V or 24V nominal (± 20%), negative ground

SUPPLY CURRENT

100 ma (maximum), (± 20%)

COMMUNICATION PORT

RS 422, 4.8 KBaud, Thomson Technology T-Net Protocol

 

to MEC 2/MEC 20 8 conductor #22 AWG (min) Shielded/

 

Twisted cable (1000 ft Max), Plug-in RJ45 Connector

DIGITAL CONTACT INPUT

Close to DC Negative

TEMPERATURE RANGE

-40°C to +50° C

 

 

ENVIRONMENTAL

Faceplate NEMA 12, Rear Enclosure NEMA 1

DIMENSIONS

6.0” W x 6.0” H x 3.0” D

Flush mount adapter option

(7.0” w x 7.0” H)

MOUNTING

Surface Mount (Standard), Flush-mount (Optional) Rear

 

Enclosure conduit box c/w Qty 8 1/2” knockouts

 

 

ORDERING INFORMATION

The EAP 110 may be ordered separately or in conjunction with unit mount control panels or engine controllers. When ordering for use with existing MEC 2/MEC 20 engine controller applications in the field, contact Thomson Technology for additional information regarding software/hardware compatibility.

The EAP 110 is supplied from the factory with standard alarm labeling for MEC 2* or MEC 20* engine controllers which are applied to meet NFPA 110 Level 1/NFPA 99 or CSA 282 alarm requirements. The standard EAP 110 can be labeled and programmed for alternate alarm configurations (consult Thomson Technology for further information). When specified, the optional flush mount adapter plate is supplied loose with the standard Annunciator for field installation.

EXAMPLE:

EAP 110 – S

BASIC MODEL

 

 

 

 

 

 

 

 

 

 

MOUNTING

 

 

 

 

 

 

 

 

 

 

S = SURFACE(Standard)

 

 

 

*Note: For MEC 2 / MEC 20 details refer to separate brochures.

F = FLUSH(Optional)

 

 

 

 

 

 

 

 

 

 

EXTERNAL CONNECTIONS

EAP 110

J1

 

Annunciator

 

Ext1 Ext2 Ext3 Ext4

B+ B-

O

O

O

O

 

O

O

Communication

Cable**

GRD

No

Connection

1000' maximum cable length

J6

Expansion

Port

J7

Communication

Port

B+ B-

 

O

O

MEC 2/20

Engine

Controller

External Alarm Sensing Contacts (optional use

as required)

** 8 conductor Shielded Twisted Cable c/w RJ45 connectors.

NOTE: Specifications subject to change without notice.

CL057 REV 0 02/07/01

+

-

12-24V Engine Cranking Battery

THOMSON TECHNOLOGY INC. • 9087A - 198th STREET, LANGLEY, BC CANADA V1M 3B1

TELEPHONE: (604) 888-0110 • FAX: (604) 888-3381E-MAIL: info@thomsontechnology.com • www.thomsontechnology.com