5.2C Auxiliary relay operation

FOR HVAC INSTALLER ONLY

White

UA Base Unit

 

optional DAMPER

Yellow

Red

Blue

Green

 

 

 

 

 

 

 

 

24 VAC

 

 

 

DEH 3000 Wiring Diagram

DMP COMP FAN

WARNING: TO AVOID TRANSFORMER DAMAGE ONLY CONNECT WHITE WIRE TO CONTROL IF DAMPER IS USED.

The white wire controls the optional motorized damper that can be installed into a fresh air duct. This provides the ability to control when fresh air is introduced into the building by using the ventilation timer function labeled “DMP” on the control (See Section 3.7). If the motorized damper is not used, DO NOT CONNECT THE WHITE WIRE

TO THE CONTROL OR DAMAGE TO THE TRANSFORMER MAY RESULT. Simply leave the (DMP) terminal unused if the damper is not used, and cap off the white lead fro mthe Ultra-Aire base unit.

5.2C Auxiliary relay operation

At times it may be desirable to coordinate fan operation of the central heating/cooling system with dehumidifier operation. The DEH 3000 features a relay that provides this ability. The relay terminals labeled NC, COM and NO operate according to the following chart:

Dehumidification

 

 

Operation

COM/NO

COM/NC

 

 

 

ON

CLOSED

OPEN

OFF

OPEN

CLOSED

Common uses (assuming standard thermostat wiring color schemes as noted):

Disengage A/C during dehumidification Redirect the yellow thermostat wire to the NC terminal. Wire the yellow wire from the A/C to the COM (B) terminal.

Engage A/C during dehumidification

Connect a wire from the “R” terminal on the the thermostat to the “com” terminal on the DEH 3000. Connect a wire from the “NO” terminal on the DEH 3000 to the “Y1” terminal on the thermostat.

5.2D Dehumidifier lockout/activation AC sensor

The control has the ability to activate the dehumidifier or deactivate the dehumidifier when the air conditioner is running.

Standard wire colors for thermostats are as follows:

Description

Color

Terminal code

 

 

 

24VAC Return

Red

R

 

 

 

Call for Heat

White

W or W1

 

 

 

Force Fan On

Green

G

 

 

 

Compressor

 

 

Call for Cooling

Yellow

Y or Y1

 

 

 