Inspection/Unpacking

Inspection

Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the pallet. Refer to labels or documentation attached to packing material.

Unpacking

Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all original crating and packing materials for return to the shipping agent. The warranty does not apply to damage incurred during shipping. Ensure that the rated capacity and the model number specified on the nameplate conform to the order specifications.

Installation Precautions

1.Install the unit in a well-ventilated location; allow at least 4 inches (10 cm) on all sides for air ventilation and for maintenance.

2.Install the unit in a stable, level and upright position that is free of excessive vibration.

3.Install the unit where the ambient temperature is within 32 – 104 °F (0 – 40 °C).

4.DO NOT install the UPS in areas that are subject to high humidity.

5.DO NOT install the UPS in areas that allow exposure to direct sunlight.

6.DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal particles, or flammable gases.

7.DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground will reduce the effects of electrical noise and will reduce the potential for electrical shock.

8.DO NOT install the UPS in areas that would allow fluids or any foreign object to get inside the UPS.

9.The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that are operating near by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or powered from a different source than that of the affected equipment.

10.After ensuring that all power sources are turned off and isolated in accordance with established lockout/tagout procedures, connect the power source wiring of the correct voltage to the input terminals of the UPS.

11.Connect the output terminals of the UPS to the load (refer to NEC Article 300 – Wiring Methods and Article 310 –

Conductors For General Wiring). Size the branch circuit conductors in accordance with NEC Table 310.16.

Conductor Routing and Grounding

1.Use separate metal conduits for routing the input power, output power, and control circuits.

2.Follow the wire size and tightening torque specifications listed on page 4.

3.Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise.

4.A separate ground cable should be run inside the conduit with the input power, output power, and control circuits.

THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.

Operating Precautions

1.The UPS should not be used with a load that has a rated input that is greater than the rated output of the UPS.

2.DO NOT use the UPS to provide power to motors that require high starting current or with motors that require a long starting time, such as vacuum cleaners/machine tools (oversizing the UPS for lock rotor current would be required).

3.DO NOT attempt to disassemble, modify, or repair the UPS. Repairs and servicing should only be performed by Toshiba

Field Service personnel.

4.Access panels should be removed only by Toshiba Field Service personnel.

5.Turn the power on only after installing ALL of the covers.

6.If the UPS should emit smoke, produce an unusual odor, or make sound, turn the power off immediately.

2

1600XP Series Quick Installation Guide

Page 2
Image 2
Toshiba 1600 XP UPS Inspection/Unpacking, Installation Precautions, Conductor Routing and Grounding, Operating Precautions

1600 XP UPS specifications

The Toshiba 1600 XP Uninterruptible Power Supply (UPS) is designed to provide robust backup power and exceptional electrical protection for critical equipment in various applications, including data centers, telecommunications, and industrial settings. This model is geared toward ensuring high reliability in power management, safeguarding against power disturbances that could jeopardize operational continuity.

One of the significant features of the Toshiba 1600 XP UPS is its high efficiency rating. Operating at up to 94% efficiency, it minimizes energy consumption and reduces overall operating costs. This efficiency also contributes to lower heat generation, which helps maintain optimal operating conditions and prolongs the lifespan of both the UPS and connected equipment.

The 1600 XP utilizes advanced double conversion online technology, which provides clean and stable power by continuously regulating voltage and frequency. This technology keeps connected loads free from surges, sags, and transients, ensuring that sensitive electronics operate without complications even in the event of a power failure.

This UPS model is equipped with a modular design, allowing for easy scalability and maintenance. As power demands grow, users can expand the system seamlessly by adding additional modules. Furthermore, the modular architecture simplifies maintenance, as components can be replaced without needing to power down the entire system.

The Toshiba 1600 XP also includes user-friendly features such as an intuitive LCD display, which provides real-time information on UPS status, power consumption, and battery health. Alarm notifications and event logging capabilities further enhance monitoring and management, enabling proactive maintenance and swift response to any issues.

Another characteristic of the Toshiba 1600 XP is its extensive battery management system. This feature extends battery life through smart charging cycles and temperature compensation, ensuring reliable backup power when it's most needed. Additionally, the UPS can be integrated with advanced communication protocols, allowing seamless interaction with building management systems for centralized monitoring.

In summary, the Toshiba 1600 XP UPS is a reliable and efficient power protection solution that combines advanced technology with user-friendly features, making it an ideal choice for industries needing uninterrupted power supply. With its modular design, high efficiency, and robust protection capabilities, it stands out as a valuable asset for maintaining operational integrity in today’s power-sensitive environments.