41600XP Series Quick Installation Guide
4
Initial UPS Startup
The rst time the UPS is activated after being shipped from the factory, an initialization program will require the
operator to input the following parameters. The UPS display operation is explained in detail on pages 32-62
The rst screen during the initial startup sequence requires the operator to select the nominal input voltage. 1.
Select from 208V, 230V, or 240V, and press the Write key. If the command has been accepted, the word
“Successful” will appear at the bottom left side of the display.
Repeat the process in step 1 in selecting the 2. Rated Vout.
Repeat the process in step 1 in selecting the3. Input Frequency.
Use the keypad to type in the 4. current date in the format: Mon 10/05/2009. and press Write.
Use the keypad to type in the 5. current time in 12 hour format: 12:15 PM and press Write.
The Main screen is now displayed. Verify the UPS is in 6. BYPASS mode. The mode (lower right side of the
display) should display Bypass. If it does not display Bypass, press and momentarily hold the STOP button.
With the UPS in bypass mode, cycle power to the UPS as follows:7.
At the rear of the UPS switch the main circuit breaker MCCB to OFF.•
Leave the UPS off until the DC bus is safely discharged (approximately 5-10 minutes).•
Restart the UPS by switching the main circuit breaker ON.•
The table below summarizes the initialization parameters:
ID Command Options
111 Rated Vin Select from 208V, 230V, or 240V, and press Write.
215 Rated Vout Select from 208V, 230V, or 240V, and press Write.
141 Input Frequency Select from 60Hz or 50Hz, and press Write.
634 UPS Date Input the date in this format: Mon 10/05/2009. and press Write.
635 UPS Time Input the current time in 12 hour format: 12:15 PM and press Write.
FAQ Sheet
Following are some Frequently Asked Questions concerning installation of the 1600EP Series UPS.
NOTICE The batteries for the UPS must be installed while the UPS is energized.
FAQ #1 My Output is ~85V.
Problem: Output is wired across the incorrect output terminals. The voltage across terminals 5 – 6(X2 – N) will
be approximately 85V.
Solution: The correct 120V output terminals are 4 – 6 (X1 – N), and 7 – 6 (X3 – N).
FAQ #2 My Output is other than 85, 120, 208 or 240V.
Problem: The Terminal strip jumper may be installed incorrectly for the incoming voltage.
Solution: Check that the Jumper wire/buss strip is installed correctly for the incoming voltage.
Toshiba Contact Information: Toshiba Industrial Division, 13131 West Little York Road, Houston, TX 77041
Tel: US 800-231-1412, Canada 800-872-2192, Mexico 01/800/527-1204 www.toshiba.com/ind