4.Access panels should be removed only by Toshiba Field Service personnel.
5.Turn the power on only after installing ALL of the covers.
6.If the UPS should emit smoke, produce an unusual odor, or make sound, turn the power off immediately.
When operating in the inverter mode, placing the breaker in the OFF position will switch the UPS to the battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be in the bypass mode at the time that the breaker is placed in the OFF position for the UPS to shutdown power to the load.
NOTICE
Wait at least 5 minutes after an Emergency Power Off (EPO) before resetting the UPS breaker. This allows the UPS circuitry to fully discharge. The UPS could be damaged if the unit is not fully discharged before the breaker is reset.
Hardwire Connections
Remove the terminal cover plate on the
Jumper Position for 208V input
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 11 | 12 | 13 | 14 | 15 | 16 | 17 |
L1 | L2 | G | X1 | X2 | N | X3 | G | 208 | COM | 240 | EPO1 | EPO2 REMOTE1 | REMOTE2 |
120 V 120 V
208 Vin
208 V
240 V
Jumper Position for 240V input
Jumper
1 | 2 | 3 |
|
| 4 | 5 | 6 |
| 7 | 8 |
|
| 11 | 12 | 13 | 14 | 15 | 16 | 17 | |||||||||
L1 | L2 |
|
| G | X1 | X2 | N | X3 |
|
| G | 208 | COM | 240 | EPO1 | EPO2 | REMOTE1 | REMOTE2 | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
240 Vin
120 V 120 V
208V
240 V
Jumper
Note 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with the provided jumper wire/bus bar. DO NOT jumper terminal 13 to 12 or 11. Factory Setting is 208Vac. Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.
Note 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with the provided jumper wire/bus bar. DO NOT jumper terminal 11 to 12 or 13. Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.
Note 3 –
NOTICE
DO NOT jumper Terminals 11 and 13 together. Doing so could damage the UPS.
Output Terminal Connections for 208/240Vin
Connect the load to the output terminals according the load voltage requirements. See the Output Terminal Voltages table to the right.
Output Terminal Voltages
Vout | Terminal Lugs | |
120 Vout | X3 | - N, or X1 - N |
208 Vout | X3 | - X2 |
240 Vout | X3 | - X1 |
1600EP Series Quick Installation Guide | 33 |