Wire Size and Tightening Torque
Use the following table to select the recommended wire size and terminal lug tightening torque for I/O wire connections.
| Terminal | AWG | AWG | AWG | AWG | AWG | AWG | AWG | Tightening | ||
Item | Torque | ||||||||||
Number | 3.6 kVA | 6 kVA | 8 kVA | 10 kVA | 22 kVA | ||||||
| |||||||||||
AC Input Lines | 1 and 2 | 12 (8) | 12 (8) | 10 (8) | 8 | (1/0) | 6 (1/0) | 4 (1/0) | 1 (1/0) | 14.2 (1.56) | |
AC Output Lines | 4, 5, and 7 | 12 (8) | 12 (8) | 10 (8) | 8 | (1/0) | 6 (1/0) | 4 (1/0) | 1 (1/0) | 14.2 (1.56) | |
AC Output Neutral | 6 | 12 (8) | 12 (8) | 10 (8) | 8 | (1/0) | 6 (1/0) | 4 (1/0) | 1 (1/0) | 14.2 (1.56) | |
Ground | 3 and 8 | 12 (8) | 12 (8) | 10 (8) | 8 | (1/0) | 6 (1/0) | 4 (1/0) | 1 (1/0) | 14.2 (1.56) | |
EPO Switch | 14 and 15 | 16 | 16 | 16 |
| 16 | 16 | 16 | 16 | 9.0 (0.99) | |
Remote Switch | 16 and 17 | 16 | 16 | 16 |
| 16 | 16 | 16 | 16 | 9.0 (0.99) |
Note: Wire size presented as the recommended size followed by a bold number in () that is the maximum wire size the terminal block can accommodate. See the manual, page 48, for
FAQs
Below are some Frequently Asked Questions concerning installation of the 1600EP Series UPS.
NOTICE
The batteries for the UPS must be installed while the UPS is energized.
FAQ #1 My Output is ~85V.
Problem: Output is wired across the incorrect output terminals. The voltage across terminals 5 – 6(X2 – N) will be approximately 85V.
Solution: The correct 120V output terminals are 4 – 6 (X1 – N), and 7 – 6 (X3 – N). FAQ #2 My Output is other than 85, 120, 208 or 240V in Bypass mode.
Problem: The Terminal strip jumper may be installed incorrectly for the incoming voltage.
Solution: Check that the Jumper wire/buss strip is installed correctly for the incoming voltage.