Black Gold Single Phase Uninterruptible Power Supply Systems Guide Specifications
2.0kVA Industrial Rackmount
waveform modulated by the PWM control using the 16 KHz switching frequency sinewave. The
a self-extinguishing function and a high switching speed.
4.2Modes of Operation
4.2.1Emergency (Battery Backup)
In the event the AC power from the utility system fails, the DC power is supplied from the batteries to the chopper and to the inverter to provide a continued and stable AC power supply to the load without interruption.
4.2.2Normal (Inverter)
The rectifier converts AC to DC to power the inverter, which supplies power to the critical load and simultaneously float charging the batteries.
4.2.3Battery Charge
The charger will float charge the batteries while no load is being powered by normal mode.
4.2.4Static Bypass
The load is being powered by an alternate source by being transferred from normal mode to bypass mode by the bypass switch. This mode is used during overload and maintenance repair. Power is conditioned by M.O.V.'s and a line filter during bypass operation.
5.0UPS Input
5.1System Rating The UPS's are sized to supply a load with a power factor of 0.70.
5.2Electrical Requirements
Voltage: | 120 VAC Single Phase | |
Frequency: | 50 or 60 Hz | +/- 5 Hz |
Input Harmonic Distortion: | less than 10% THD (current) |
Input capacity: 1.0 times output capacity
Input power: approximately 1.0 power factor (unity)
5.2.2Battery Bus
Volts: | 2.0 KVA 72 VDC nominal |
Backup time: 6 mins @ full load/18 mins @ half load
Page 2 of 5