G9000 Series 80/100/160/225 KVA UPS
Model Number | T90S3S08KS6XSN | T90S3S10KS6XSN | T90S3S16KS6XSN | T90S3S22KS6XSN | |
Capacity | KVA/KW | 80/72 | 100/90 | 160/144 | 225/202.5 |
Topology |
| True |
| ||
Input | Voltage | 480 V, | |||
| Voltage Range |
| 480 V, |
| |
| Power Factor |
| Greater than 0.99 |
| |
| Current THD |
| <3% at 100% Load (No Input Filter Required) |
| |
| Frequency |
| 60 Hz (± 10%) |
| |
Output | Voltage |
| 480 V, |
| |
| Frequency |
| 60 Hz, ±0.01% (In |
| |
| Voltage Regulation |
| ±1.0% (0.5% Typical) |
| |
| Power Factor |
| 0.9 Lagging |
| |
| Power Factor Range |
| 0.9 to 1.0 Lagging |
| |
| Voltage THD |
| <2% for Linear Load, <5% for |
| |
| Overload (Inverter) |
| 125% for 2 Minutes; 150% for 60 Seconds |
| |
| Overload (Bypass) |
| 1000% for One Cycle |
| |
Battery | DC Link |
| 480 VDC |
| |
| Ripple Voltage |
| ±0.23% |
| ±0.29% |
Environment | Temperature Range |
| 32° to 104°F (0° to 40°C) |
| |
| Relative Humidity |
| 5% to 95% |
| |
| Heat Rejection | 11,307 BTUs/Hour | 14,133 BTUs/Hour | 19,408 BTUs/Hour | 27,292 BTUs/Hour |
| Efficiency | 95.6% | 95.6% | 96.5% | 96.5% |
| Efficiency (20% Load) | 92.5% | 92.5% | 94.6% | 94.7% |
| Altitude |
| 7380 Feet Maximum Without Derating (2250 Meters) |
| |
| Audible Noise |
| 69.5 dBA at 1 Meter |
| |
Dimensions | Dimensions (W x D x H) | 27.6 x 32.8 x 80.6 in. | 35.4 x 32.8 x 80.6 in. | ||
|
| (700 x 832 x 2047 mm) | (900 x 832 x 2047 mm) | ||
| Weight | 835 lbs. (388 kg) | 855 lbs. (388 kg) | 1160 lbs. (526 kg) | 1230 lbs. (558 kg) |
Features | Digital Signal Processor (DSP) Control, Fully Digital IGBT Converter & Inverter, High Efficiency Over Wide Load Range, | ||||
| |||||
|
| RS232 and Dry Contact Interface, Small Footprint, Lightweight Design |
| ||
Standards | UL 1778, CUL, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), FCC Class A, Article 47, Part 15.B | ||||
Warranty |
| Three Years Onsite (Optional Two Year Extended Warranty) |
| ||
|
| See Toshiba Warranty Policy for Full Details |
| ||
Service |
|
|
| G9000 Series UPS Module |
|
|
Bypass Input |
|
|
|
480 VAC |
|
|
|
Optional Jumper for |
| ||
|
|
| |
Ground | ac/dc IGBT | Dc/Ac IGBT | Static Transfer Switch |
| |||
AC Input | Converter | Inverter |
|
|
|
| |
480 VAC |
|
|
|
|
|
| |
|
|
| |
Ground |
| DC/DC IGBT |
|
|
|
| |
|
| Chopper |
|
Battery
Cabinet
AC Output
480VAC
Ground
| Two G9000 UPS Modules in |
|
AC | Parallel Configuration | TIE |
INPUT | CABINET | |
|
| AC |
|
| OUTPUT |
| UPS #1 |
|
UPS #2
UPS ADJUSTABLE SPEED DRIVES | MOTORS | CONTROLS INSTRUMENTATION PLC | |||||||||
|
|
|
|
|
|
|
|
|
|
| Available Through: |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
| |||||
INDUSTRIAL DIVISION |
|
| |||||||||
13131 West Little York Road, Houston, Texas 77041 |
|
| |||||||||
Tel | Fax |
|
| ||||||||
US | Canada |
| |||||||||
www.toshiba.com/ind |
| *UPSG9000MMCT081209* | |||||||||
Copyright 12/2008 UPS G9000 B05 23 |
|