Separate type LF470/LF612 flowmeter
Terminal board
Thick walled steel conduit
Signal cable
Connected detector
Excitationcable
|
| IV wire | |
|
| 5.5 mm2 or more | |
|
| Grounded with 100Ω or less | |
|
| ground resistance | |
| Power switch |
| |
| (External | ||
|
| [Instrument panel : ordered separately] | |
|
| Grounded with 100Ω or less | |
|
| groundresistance | |
|
| Power supply | |
|
| Current output (4~20mAdc) | |
|
| or PROFIBUS | |
|
| Digital output 1 | |
|
| Signal common for DI and DO | |
|
| Digital output 2 | |
|
| Digital input | |
Power cable | Digital input cable | (20~30Vdc) | |
Grounded with 100Ω or less | |||
(CVV) | |||
|
| groundresistance |
Figure 6. Separate type LF470/LF612 flowmeters wiring Diagram
Table 1. LF612 Converters Signal Table
Symbol | Description |
| Cable |
|
L1 (+) | Power supply |
| Power cable (CVV) |
|
L2 (-) |
|
| ||
|
|
|
| |
GND | Ground (for arrester) |
|
|
|
FG | Frame ground |
|
|
|
DI | Digital Input (20~30Vdc) |
|
|
|
DO1 | Digital Output 1 |
|
|
|
DO2 | Digital Output 2 |
|
|
|
COM | Signal Common for DI, DO1, DO2 |
| I/O cable | |
|
|
|
+Current Output (4~20mAdc)
-or PROFIBUS
X | Excitation Output |
| Excitation cable |
|
Y |
|
| ||
E |
|
|
|
|
A | Signal Input |
| Signal cable |
|
B |
|
| ||
G |
|
|
|
|
5