1. Overview

4

1. Overview

By using RS-485 Option Unit, a network can be constructed that allows communication between a host computer and multiple ASD units. A maximum of 32 Option Units can be connected on the same network. And two ASDs can be connected to one Option Unit. A maximum of 64 ASDs can be connected on the same network. (If ASD has a CPU whose version is V104 or V103, a maximum of 32 ASDs can be connected on the same network.)

2. Communication specifications

Item

Specifications

Interface

Conforming to EIA RS485 standard

Configuration

4-wire, bus type (terminating resistor is necessary at

 

each end of system)

Communication Distance

1,000m maximum

Connection Points

32 units maximum

Number of ASDs per one Option Unit

2 units maximum

Number of ASDs on the Same Network

64 units maximum (If ASD has a CPU whose version

 

is V104 or V103, a maximum of 32 ASDs can be

 

connected on the same network.)

Communication Line Isolation

Not isolated

Synchronization Method

Start-stop synchronization

Error Detection Method

Parity, checksum

Communication Speed

1200/2400/4800/9600 baud selectable (parameter

 

and switch selection)

Data Code

ASCII code, binary code

Other

Time-out function available