I. ELECTRIC HEATERS

I. ELECTRIC HEATERS

Electric heaters, if used, are to be installed in the air han- dling device according to the instructions accompanying the air handler and the heaters.

J. START CONTROL

Some models have quick start components which are factory installed. For models that do not have factory installed start components, provisions are made for a field installed start kit accessory. When adding an accessory, follow the instructions provided with the kit.

K. OUTDOOR THERMOSTAT

An outdoor thermostat TAYSTAT250B may be field installed. For data, see wiring diagram attached to unit and instruc- tion sheet packaged with outdoor thermostat.

L. SEACOAST SALT SHIELD

Units installed within one mile of salt water including seacoasts and inland waterways, require the addition of BAYSEAC001 (Seacoast Kit) at the time of installation.

IMPORTANT:

See Limited Warranty information in Use and Care Manual.

Installer’s Guide

M. TROUBLESHOOTING

TROUBLESHOOTING CHART — WHAT TO CHECK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

REF

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

CONTROL

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

WHAT

HIGH

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

.

 

 

 

DEFROST

 

 

 

 

 

 

 

 

 

LOW

 

 

 

STUCK

REF

 

 

AIR

 

 

CIR

SOVCHECK

 

 

 

 

 

 

 

 

 

CONTACTOR

 

 

LOW

 

EXCESSIVE

RES

 

 

 

 

 

DEFROST

 

 

TO

 

 

 

 

 

 

 

 

 

REF

 

 

TXV

RES .

 

 

 

 

 

 

 

START

 

 

 

 

 

 

 

.

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

 

 

.

 

 

COIL

 

 

 

 

POWERVOLTAGE

RUN

 

 

VOLTAGE

 

 

 

INEFFICIENT

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

I

 

 

 

VALVE

 

 

SYSTEM FAULTS CHECK COMPRESSOR

START

 

 

CONTACTOR

 

 

 

.

 

 

D

 

SOV

 

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

 

.

 

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONCONDENSABLESSTUCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

EVAP

RECIRCULATIONRESTRICTIONS

RELAY

 

 

 

 

 

 

 

 

 

 

 

UNDERCHARGE.

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOSTATCOMPRESSOROVERCHARGE

 

 

SUPERHEAT

 

DEFECTIVE

 

 

 

 

 

 

CAPACITORCAPACITORCONTACTS

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

SUPPLYWIRING

 

 

RELAY

WIRING

 

 

FUSE COMP

 

 

 

AIRFLOWLEAKINGLEAKING

 

 

 

MODE

 

IOL

 

 

 

 

 

LOAD

 

 

OPEN

 

 

 

 

 

DEFDEF

 

 

 

 

 

 

 

 

 

 

 

COIL

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

. .

REFRIGERANT CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Head Pressure Too High

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

P

S

P

S

 

 

 

S

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

P

S

 

 

 

 

P

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Head Pressure Too Low

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

 

 

 

S

S

 

S

S

S

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

 

 

 

S

S

 

S

S

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Pressure Too High

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

P

 

 

 

 

S

 

 

P

 

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

S

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Pressure Too Low

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

S

P

S

 

S

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Refrig. Floodback (TXV)

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I.D. Coil Frosting

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Runs

 

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

 

S

S

 

 

 

S

P

S

S

S

S

 

Inadequate or No Cooling/Htg

 

H

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

S

 

 

 

S

P

S

S

 

S

 

ELECTRICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor & O.D. Fan

 

C

P

P

 

 

 

 

 

S

P

S

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Won’t Start

 

 

H

P

P

 

 

 

 

 

S

P

S

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Will Not Start

 

C

 

P

S

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

But O.D. Fan Runs

 

 

H

 

P

S

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O.D. Fan Won’t Start

 

C

 

P

 

P

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

P

 

P

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Hums But Won’t Start

 

C

 

 

 

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Cycles on IOL

 

C

 

P S P S S S

 

 

 

 

P S P P S

 

S S

 

S

 

 

S

 

 

 

 

H

 

P S P S S S

 

 

 

 

P S P P S

 

S

 

 

S P

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I.D. Blower Won’t Start

 

C

P

P

 

 

 

 

 

S

P

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

P

P

 

 

 

 

 

S

P

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEFROST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Won’t Initiate

Defrost

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost Terminates on Time

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Icing Up

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

 

S

 

 

P

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C - Cooling

H - Heating

P - Primary Causes

 

S - Secondary Causes

* - 3 Phase Only

 

 

 

 

 

 

 

 

TYPICAL FIELD HOOK-UP DIAGRAMS

Notes:

1.Be sure power supply agrees with equipment nameplate.

2.Power wiring and grounding of equipment must comply with local codes.

3.Low voltage wiring to be No. 18 AWG minimum conductor.

4.ODT-B must be set lower than ODT-A.

5.If outdoor thermostats (ODT) are not used, connect W1 to W2 and W3.

6.N/A to programmable thermostat.

LEGEND

FACTORY WIRING

FIELD WIRING

18-BC62D1-1