I. ELECTRIC HEATERS
Electric heaters, if used, are to be installed in the air han- dling device according to the instructions accompanying the air handler and the heaters.
J. START CONTROL
Some models have quick start components which are factory installed. For models that do not have factory installed start components, provisions are made for a field installed start kit accessory. When adding an accessory, follow the instructions provided with the kit.
K. OUTDOOR THERMOSTAT
An outdoor thermostat TAYSTAT250B may be field installed. For data, see wiring diagram attached to unit and instruc- tion sheet packaged with outdoor thermostat.
L. SEACOAST SALT SHIELD
Units installed within one mile of salt water including seacoasts and inland waterways, require the addition of BAYSEAC001 (Seacoast Kit) at the time of installation.
IMPORTANT:
See Limited Warranty information in Use and Care Manual.
Installer’s Guide
M. TROUBLESHOOTING
TROUBLESHOOTING CHART — WHAT TO CHECK
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| . |
|
|
| REF |
|
|
| * |
|
|
|
|
|
|
|
|
|
|
| CONTROL |
|
|
|
|
|
|
| D |
|
|
|
|
|
|
|
|
| ||||
| WHAT | HIGH |
|
|
|
|
|
|
|
|
|
|
| . |
|
|
| . |
|
|
| DEFROST |
| ||||||
|
|
|
|
|
|
|
| LOW |
|
|
| STUCK | REF |
|
| AIR |
|
| CIR | SOVCHECK |
|
|
| ||||||
|
|
|
|
|
| CONTACTOR |
|
| LOW |
| EXCESSIVE | RES |
|
|
|
|
| DEFROST |
| ||||||||||
| TO |
|
|
|
|
|
|
|
|
| REF |
|
| TXV | RES . |
|
|
| |||||||||||
|
|
|
| START |
|
|
|
|
|
|
| . |
|
| . |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
| . |
|
|
|
|
| . |
|
| COIL |
|
|
| |||||
| POWERVOLTAGE | RUN |
|
| VOLTAGE |
|
|
| INEFFICIENT |
|
| O |
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
| . |
|
|
| I |
|
|
| VALVE |
|
| ||||||||||
SYSTEM FAULTS CHECK COMPRESSOR | START |
|
| CONTACTOR |
|
|
| . |
|
| D |
| SOV |
|
|
|
| ||||||||||||
|
|
|
| VOLTAGE |
|
|
|
|
| . |
|
|
|
| CONTROL |
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NONCONDENSABLESSTUCK |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
| TRANSFORMER |
|
| EVAP | RECIRCULATIONRESTRICTIONS | RELAY |
| ||||||||||||||
|
|
|
|
|
|
|
|
|
| UNDERCHARGE. |
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
| THERMOSTATCOMPRESSOROVERCHARGE |
|
| SUPERHEAT |
| DEFECTIVE |
| |||||||||||||
|
|
|
|
| CAPACITORCAPACITORCONTACTS |
|
|
|
|
|
|
| AIRFLOW |
|
| ||||||||||||||
|
|
| SUPPLYWIRING |
|
| RELAY | WIRING |
|
| FUSE COMP |
|
|
| AIRFLOWLEAKINGLEAKING |
| ||||||||||||||
|
| MODE |
| IOL |
|
|
|
|
| LOAD |
|
| OPEN |
|
|
|
|
| DEFDEF | ||||||||||
|
|
|
|
|
|
|
|
|
|
| COIL | . |
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| . . | ||
REFRIGERANT CIRCUIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Head Pressure Too High |
| C |
|
|
|
|
|
|
|
|
|
|
|
| P | P | S | P | S |
|
|
| S |
|
|
|
| ||
| H |
|
|
|
|
|
|
|
|
|
|
|
| P | P | S |
|
|
|
| P | S |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
Head Pressure Too Low |
| C |
|
|
|
|
|
|
|
|
|
|
| S | P |
|
|
|
|
| S | S |
| S | S | S | P |
| |
| H |
|
|
|
|
|
|
|
|
|
|
| S | P |
|
|
|
|
| S | S |
| S | S |
| P |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Suction Pressure Too High |
| C |
|
|
|
|
|
|
|
|
|
|
| S | P | P |
|
|
|
| S |
|
| P |
| P |
| ||
| H |
|
|
|
|
|
|
|
|
|
|
| S |
|
|
|
|
|
|
| S |
|
| P |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Suction Pressure Too Low |
| C |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
|
| S | P | S |
| S |
|
| |
| H |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
| S | S |
| S |
| S |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
Liquid Refrig. Floodback (TXV) |
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
| P |
| |
| H |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
| P |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
I.D. Coil Frosting |
|
| C |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
| S | S |
|
|
|
|
|
|
|
|
|
| H |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Compressor Runs |
|
| C |
|
|
|
|
|
|
|
|
|
|
| S | P |
| S | S |
|
|
| S | P | S | S | S | S |
|
Inadequate or No Cooling/Htg |
| H |
|
|
|
|
|
|
|
|
|
|
| S | P |
|
| S |
|
|
| S | P | S | S |
| S |
| |
ELECTRICAL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor & O.D. Fan |
| C | P | P |
|
|
|
|
| S | P | S | P | P |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Won’t Start |
|
| H | P | P |
|
|
|
|
| S | P | S | P | P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor Will Not Start |
| C |
| P | S | P | S | S | S |
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
But O.D. Fan Runs |
|
| H |
| P | S | P | S | S | S |
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
O.D. Fan Won’t Start |
| C |
| P |
| P |
|
| S |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H |
| P |
| P |
|
| S |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Compressor Hums But Won’t Start |
| C |
|
|
| P | S | S | S |
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H |
|
|
| P | S | S | S |
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
Compressor Cycles on IOL |
| C |
| P S P S S S |
|
|
|
| P S P P S |
| S S |
| S |
|
| S |
|
|
| ||||||||||
| H |
| P S P S S S |
|
|
|
| P S P P S |
| S |
|
| S P |
| S |
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||
I.D. Blower Won’t Start |
| C | P | P |
|
|
|
|
| S | P | S |
| S |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H | P | P |
|
|
|
|
| S | P | S |
| S |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
DEFROST |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit Won’t Initiate | Defrost |
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| P | P | P | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Defrost Terminates on Time |
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| H |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
| P | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Unit Icing Up |
|
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| H |
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
| S | S |
|
| S |
|
| P |
| P | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
C - Cooling | H - Heating | P - Primary Causes |
| S - Secondary Causes | * - 3 Phase Only |
|
|
|
|
|
|
|
|
TYPICAL FIELD
Notes:
1.Be sure power supply agrees with equipment nameplate.
2.Power wiring and grounding of equipment must comply with local codes.
3.Low voltage wiring to be No. 18 AWG minimum conductor.
4.
5.If outdoor thermostats (ODT) are not used, connect W1 to W2 and W3.
6.N/A to programmable thermostat.
LEGEND
FACTORY WIRING
FIELD WIRING