Fault diagnosis
FAULT DIAGNOSIS BY REMOTE CONTROLLER
In the ARC433A series, the temperature display sections on the main unit indicate corresponding codes.
1.When the TIMER CANCEL button is held down for 5 seconds, a “ ” indication flashes on the temperature display section.
F F
O N
HOME LEAVE | ON/OFF |
|
|
| |
POWERFUL | TEMP |
|
MODE | FAN |
|
SILENT | SENSOR SWING |
|
ON | CANCEL | TIMER CANCEL button |
OFF |
| It cancels the timer setting. |
| TIMER |
|
2.Press the TIMER CANCEL button repeatedly until a continuous beep is produced.
•The code indication changes as shown below, and notifies with a long beep.
| CODE | MEANING | |
| 00 | NORMAL | |
SYSTEM | U0 | REFRIGERANT SHORTAGE | |
U2 | DROP VOLTAGE OR MAIN CIRCUIT OVERVOLTAGE | ||
| |||
| U4 | FAILURE OF TRANSMISSION (BETWEEN INDOOR UNIT AND OUTDOOR UNIT) | |
| A1 | INDOOR PCB DEFECTIVENESS | |
INDOOR | A5 | HIGH PRESSURE CONTROL OR | |
A6 | FAN MOTOR FAULT | ||
UNIT | |||
C4 | FAULTY HEAT EXCHANGER TEMPERATURE SENSOR | ||
| |||
| C9 | FAULTY SUCTION AIR TEMPERATURE SENSOR | |
| EA | ||
| E5 | OL STARTED | |
| E6 | FAULTY COMPRESSOR START UP | |
| E7 | DC FAN MOTOR FAULT | |
| E8 | OPERATION HALT DUE TO DETECTION OF INPUT OVER CURRENT | |
| F3 | HIGH TEMPERATURE DISCHARGE PIPE CONTROL | |
OUTDOOR | H6 | OPERATION HALT DUE TO FAULTY POSITION DETECTION SENSOR | |
UNIT | H8 | CT ABNORMALITY | |
| H9 | FAULTY SUCTION AIR TEMPERATURE SENSOR | |
| J3 | FAULTY DISCHARGE PIPE TEMPERATURE SENSOR | |
| J6 | FAULTY HEAT EXCHANGER TEMPERATURE SENSOR | |
| L4 | HIGH TEMPERATURE AT INVERTER CIRCUIT HEATSINK | |
| L5 | OUTPUT OVERCURRENT | |
| P4 | FAULTY INVERTER CIRCUIT HEATSINK TEMPERATURE SENSOR |
NOTE
1.A short beep and two consecutive beeps indicate
2.To cancel the code display, hold the TIMER CANCEL button down for 5 seconds. The code dis- play also cancel itself if the button is not pressed for 1 minute.