Trane GAT2A0C48S41SA manual GAT2A0B42 AIRFLOW PERFORMANCE TABLE, General Data, External Static

Models: GAT2A0C60S51SA GAT2A0C48S41SA

1 20
Download 20 pages 47.45 Kb
Page 7
Image 7
GAT2A0B42 AIRFLOW PERFORMANCE TABLE

General

Data

GAT2A0B42 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE

GAT2A0B42S31SA

EXTERNAL STATIC

 

 

AIRFLOW (CFM)

 

 

(in w.g)

 

 

 

 

 

 

 

 

 

 

 

Speed Taps - 230 VOLTS

Speed Taps - 208 VOLTS

 

3

2 †

1

3

2 †

1

0

1646

1495

1358

1522

1298

1138

0.1

1599

1464

1335

1489

1285

1137

0.2

1546

1421

1313

1449

1260

1120

0.3

1488

1380

1280

1401

1233

1099

0.4

1425

1329

1233

1348

1193

1065

0.5

1353

1264

1178

1281

1140

1023

0.6

1259

1182

1108

1202

1075

958

0.7

1145

1081

995

1102

965

868

0.8

982

909

839

926

817

753

0.9

788

759

731

761

713

N/A

1.0

563

N/A

N/A

538

N/A

N/A

NOTES:

1.Values are with wet coil and without filters.

2.Contact your particular filter manufacturer for pressure drop data.

3.Electric heater pressure drop is negligible and is included within the airflow data.

4.† Factory Setting

GAT2A0B42S31SA MINIMUM HEATER AIRFLOW CFM

Heater

Minimum Air Speed Tap

 

 

 

 

With Heat Pump

Without Heat Pump

 

 

 

BAYEAAC05BK1AA

Tap 1

Tap 1

BAYEAAC05LG1AA

 

 

 

 

 

BAYEAAC08BK1AA

Tap 1

Tap 1

BAYEAAC08LG1AA

 

 

 

 

 

BAYEAAC10BK1AA

Tap 1

Tap 1

BAYEAAC10LG1AA

 

 

 

 

 

BAYEABC15BK1AA

Tap 1

Tap 1

 

 

 

BAYEABC20BK1AA

Tap 3

Tap 1

 

 

 

SEE AIR HANDLER NAMEPLATE FOR ADDITIONAL INFORMATION

Note: Heating and cooling speeds are the same, factory set at Speed Tap #2.

Pub. No. 22-1857-03

7