Trane GAT2A0C60S51SA, GAT2A0C48S41SA manual Performance Data, GAT2A0C48 AIRFLOW PERFORMANCE TABLE

Models: GAT2A0C60S51SA GAT2A0C48S41SA

1 20
Download 20 pages 47.45 Kb
Page 8
Image 8
Performance

Performance

Data

GAT2A0C48 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE

GAT2A0C48S41SA

EXTERNAL STATIC

 

 

AIRFLOW (CFM)

 

 

(in w.g)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed Taps - 230 VOLTS

Speed Taps - 208 VOLTS

 

 

 

 

 

 

 

 

3

2 †

1

3

2 †

1

 

 

 

 

 

 

 

0

1904

1711

1541

1652

1455

1305

 

 

 

 

 

 

 

0.1

1881

1687

1529

1640

1450

1288

 

 

 

 

 

 

 

0.2

1844

1666

1511

1619

1425

1271

 

 

 

 

 

 

 

0.3

1806

1637

1485

1592

1410

1249

 

 

 

 

 

 

 

0.4

1766

1602

1454

1559

1381

1231

 

 

 

 

 

 

 

0.5

1716

1560

1420

1524

1351

1198

 

 

 

 

 

 

 

0.6

1659

1513

1380

1484

1321

1165

 

 

 

 

 

 

 

0.7

1594

1458

1333

1434

1283

1127

 

 

 

 

 

 

 

0.8

1525

1395

1277

1376

1229

1067

 

 

 

 

 

 

 

0.9

1442

1310

1194

1304

1149

N/A

 

 

 

 

 

 

 

1.0

1345

N/A

N/A

1194

N/A

N/A

 

 

 

 

 

 

 

NOTES:

1.Values are with wet coil and without filters.

2.Contact your particular filter manufacturer for pressure drop data.

3.Electric heater pressure drop is negligible and is included within the airflow data.

4.† Factory Setting

GAT2A0C48S41SA MINIMUM HEATER AIRFLOW CFM

Heater

Minimum Air Speed Tap

 

 

 

 

With Heat Pump

Without Heat Pump

 

 

 

BAYEAAC05BK1AA

Tap 1

Tap 1

BAYEAAC05LG1AA

 

 

 

 

 

BAYEAAC08BK1AA

Tap 1

Tap 1

BAYEAAC08LG1AA

 

 

 

 

 

BAYEAAC10BK1AA

Tap 1

Tap 1

BAYEAAC10LG1AA

 

 

 

 

 

BAYEABC15BK1AA

Tap 1

Tap 1

 

 

 

BAYEABC20BK1AA

Tap 1

Tap 1

 

 

 

BAYEACC25BK1AA

Tap 3

Tap 2 1

 

 

 

1Not qualified for 208 V

SEE AIR HANDLER NAMEPLATE FOR ADDITIONAL INFORMATION

Note: Heating and cooling speeds are the same, factory set at Speed Tap #2.

8

Pub. No. 22-1857-03

Page 8
Image 8
Trane GAT2A0C60S51SA, GAT2A0C48S41SA manual Performance Data, GAT2A0C48 AIRFLOW PERFORMANCE TABLE