Installation- Electrical
Pressure Switch
A high pressure switch is provided to protect the compressor against exces- sive refrigeration pressure. The low pressure switch should be wired in ac- cordance with the type of freezestat that is used. Trane factory supplies two low pressure switches in the re- frigerant circuit. The electrical con- nection is dependant upon which freezestat (35 or 20 degree) is selected The pressure switch is used to protect the compressor against operation un-
der low charge or catastrophic loss of charge situations.
The low water temperature switch is provided to protect the
Important Notice
The low pressure switch should be wired to activate at refrigerant pressures of 35 psig when a 35 degree F freezestat is used; 7 psig when a 20 degree F freezestat is used. The installer should verify that the correct freezestat and low pressure switch are used in your application. Misapplication can produce a failure to the unit and cause the warranty to be voided.
HEAT EXCHANGER
7 PSIG LOW PRESSURE SWITCH USED FOR 20 DEGREE FREEZESTAT
DESUPERHEATER
COMPRESSOR
DESUPERHEATER PUMP
OR
FILTER DRIER
EXPANSION VALVE
LIQUID LINE
35 PSIG LOW PRESSURE
SWITCH USED FOR 35
DEGREE FREEZESTAT
13