Features and Benefits
Deluxe Controls
Microprocessor Design
The 24 volt deluxe design is a micro-
The Trane microprocessor board is fac- tory wired to a terminal strip to provide all necessary terminals for field connec- tions. See Figure 27 for the deluxe 24V control board.
Deluxe 24V features include: Random Start
The random start relay provides a time delay
Anti-short Cycle Timer
The
Brown-out Protection
The
Compressor Disable
The compressor disable relay provides a temporary disable in compressor operation. The signal would be provid- ed from a water loop controller in the system. It would disable the compres-
sor because of low water flow, peak limiting or if the unit goes into an unoc- cupied state. Once the compressor has been disabled, the
Generic Relay
The generic relay is provided for field use. Night setback or pump restart are two options that may be wired to the available relay. (Note: Night setback is available as factory wired). An external Class II 24VAC signal will energize the relay coil on terminals R1 and R2. Terminals C (common), NO (normally open), and NC (normally closed) will be provided for the relay contacts.
Safety Control
The deluxe microprocessor receives separate input signals from the refriger- ant high pressure switch, low suction pressure switch and condensate over- flow.
In a high pressure situation, the com- pressor contactor is
will be allowed to run. If a high pressure situa- tion occurs within one hour of the first situa- tion, the control will be placed into a manual lockout mode, halting compressor operation, and initiating the gener- al alarm.
In a low temperature situation, the low pres- sure switch will transi- tion open after the com- pressor starts. If the
switch is open for 45 seconds during compressor start, the unit will go into soft lockout mode initializing a three minute time delay and a random start of 3 to 10 second time delays. Once these delays have expired, the unit will be allowed to run. If the low pressure situation occurs again within 30 min- utes, and the device is open for more than 45 seconds, the control will be placed into a manual lockout mode, halting compressor operation, and initi- ating the general alarm.
In a condensate overflow situation, the control will go into manual lockout mode, halting compressor operation, and initiating the general alarm.
The general alarm is initiated when the control goes into a manual lockout mode for either high pressure, low pressure or condensate overflow condi- tions.
Diagnostics
Component device connections to the microprocessor board are referenced in Figure 25. Three LEDs (light emitting diodes) are provided for indicating the operating mode of the controller. See the unit IOM for diagnostics or trou- bleshooting through the use of the LEDs.
Figure 25: Deluxe 24V control board.