Trane 120 GEH Application Considerations, Hanging the Horizontal, Horizontal unit installation

Models: Model 180 GEV 120 GEH Model 012 GEH

1 28
Download 28 pages 13.12 Kb
Page 25
Image 25
Application

R

Application

Considerations

Figure 29: Horizontal unit installation

12”/ 305mm Figure 29: Horizontal unit installation

Slope: 1/4” (6.5 mm)

Hanging the Horizontal

The horizontal unit GEH A is a ceiling hung unit. It is usually applied as a totally concealed unit above an acousti- cal ceiling grid. Because the GEH A is equipped with several inlet and dis- charge arrangements, it allows for numerous application needs.

When hanging the horizontal design, the unit should be pitched approxi- mately 1/4-inch (6.4 mm) per foot toward the drain in both directions. This aids in condensate removal from the drain pan. (See Figure 29 for unit installation.)

Figure 30: Unit duct collar and hanging device installation.

Hanging Devices and Duct Attachments

All GEHA units are shipped with a fac- tory mounted hanging bracket and rub- ber isolation grommet. The 3/8 -inch (9.5 mm) all-thread and 3/8 -inch

(9.5 mm) washer and nut are field pro- vided.

One-inch duct collars are provided for field duct attachment to the supply-air outlet. The duct collars, filter racks, fil- ter and grommets are field installed.

These items are shipped in an inclo- sure external to the unit. (See Figure 30 for unit duct collar and hanging device installation.)

WSHP-PRC003-EN

25

Page 25
Image 25
Trane 120 GEH, Model 180 GEV manual Application Considerations, Hanging the Horizontal, Hanging Devices and Duct Attachments