Installation
Table 3: CTA Refrigerant Charge
Model | Refrigerant Charge | |
| ||
|
| |
CTA090A | 18.1 lbs | |
w/SCRH030 | ||
| ||
|
| |
CTA090A | 19.9 lbs | |
w/SCRH050 | ||
| ||
|
| |
CTA120A | 20.8 lbs | |
w/SCRH075 | ||
| ||
|
| |
CTA120B | 11.9 lbs | |
w/SCRH100 | (Ckt. #1 & #2) | |
|
| |
CTA180B | 16.8 lbs. (Ckt. #1) | |
w/SCRH120 | 16.0 lbs. (Ckt. #2) | |
|
| |
CTA180B | 17.5 lbs. (Ckt. #1) | |
w/SCRH150 | 16.9 lbs. (Ckt. #2) | |
|
|
*Sufficient operating charge for listed unit and 33 feet of nominally sized refrigerant piping.
Table 4: Additional Refrigerant
Tubing Sizes | Additional | Additional | ||
|
| Tubing | ||
Discharge | Liquid | Refrig. | ||
Length | ||||
|
|
| ||
|
|
|
| |
7/8" | 1/2" | 15 ft. | 1.3 lbs | |
|
|
|
| |
7/8" | 1/2" | 25 ft. | 2.2 lbs | |
|
|
|
| |
7/8" | 1/2" | 32 ft. | 2.8 lbs | |
|
|
|
| |
7/8" | 1/2" | 40 ft. | 3.5 lbs | |
|
|
|
|
Note: Amounts shown are based on 0.087 lbs of refrigerant per foot of 7/8" and 1/2" lines.
Note: For tubing over 40 feet, calculate the additional refrigerant needed, based on notes above.
Gaseous Charging
This procedure is accomplished with the unit operating. Electrical connec- tions must be complete. Do not pro- ceed until the system is ready to operate.
Procedure
1.Connect
Note: On the CTA units, the service access panel must be installed when the unit is running and being charged.
WARNING:
Hazardous Energy Sources!
Use extreme caution while servic- ing the unit when the control box access panel is removed and power is applied to the unit. Fail- ure to observe all safety precau- tions could result in death or serious injury.
2.Turn on power to the unit. Allow the system to run for five to ten minutes to stabilize operating conditions.
3.Measure airflow across the indoor coil. Compare the measurements with the fan performance data in the Data/Submittal.
4.Check suction line superheat and condenser
5.Disconnect all power to the unit.
WARNING:
Hazardous Voltage w/Capacitors!
Disconnect all electrical power, including remote disconnects and discharge all motor start/run ca- pacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be in- advertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Fail- ure to diconnect power and dis- charge capacitors before servicing could result in death or serious injury.
Note: For additional information regarding the safe discharge of capacitors, see
6.Remove the charging system from the unit and replace all access pan- els.
Electrical Wiring
CTA field wiring consists of providing power supply to the unit, installing the system indoor thermostat and provid- ing low voltage system interconnect- ing wiring. Access to electrical connection locations is shown in Fig- ures 1 through 4.
Unit Power Supply
The installer must provide line voltage circuit(s) to the unit main power termi- nals as shown by the unit wiring dia- grams in Figures 9 and 10 on page 15. Power supply must include a discon- nect switch in a location convenient to the unit. Ground the unit according to local codes and provide flexible con- duit if codes require and/or if vibration transmission may cause noise prob- lems.
CAUTION:
Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
CAUTION:
All wiring must comply with appli- cable local and national NEC codes. Type and location of dis- connect switches must comply with all applicable codes.
WARNING:
Ground Wire!
All
WARNING:
Grounding Required!
Follow proper local and state elec- trical code on requirements for grounding. Failure to follow code could result in death or serious in- jury
13