31
Electrical
Data

Table 31-1  Electrical Service Sizing Data

Fan Motors
Compressor Supply Condenser
Electrical2Qty./ RLA LRA FLA Max.
Model Characteristics Nominal HP (Ea.) Ea.) HP FLA No. HP (Ea.) MCA* Fuse Size
TC/TE/YC*275 380-415/50/3 2/10,15 18.1/27.3 110/174 5 13.1 3 .75 4.4 79 100
TC/TE/YC*305 380-415/50/3 2/15,15 27.3 174 5 13.1 3 .75 4.4 93 110
TC/TE/YC*350 380-415/50/3 2/15,15 27.3 174 5 13.1 3 .75 4.4 93 110
TC/TE/YC*400 380-415/50/3 2/15,15 27.3 174 7.5 16.6 4 .75 4.4 119 125
1/10 18.1 110
TC/TE/YC*500 380-415/50/3 3/15 27.3 174 7.5 16.6 4 .75 4.4 128 150
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
* Minimum Circuit Ampacity.

Table 31-2  Electrical Service Sizing Data  Electric Heat Module

(Electric Heat Units Only)

Models: TED/TEH 275 thru 500
Electric Heat FLA
Nominal Nominal
Unit Size Unit KW Heater (380/415V)
(Tons) Voltage 23/27 34/40 45/54 56/67 68/81
23-29 380 34.5 51.1 68.9 85.5
415 37.6 55.6
33, 43 380 51.1 68.9 85.5 103.4
415  55.6 75.1 93.2 112.7
Notes:
1. All FLA in this table are based on heater operating at 380 or 415 volts as shown above.