Trane trg-trc005-en manual Shell-and-Tube Evaporator Control

Models: trg-trc005-en

1 61
Download 61 pages 1.8 Kb
Page 32
Image 32

period three

Evaporators

notes

four rows for the downstream section. This is an attempt to ensure near-equal loading of the two coil sections when both are active.

A second concern involves the control of superheat. The cooler temperatures leaving the upstream section of coil hamper the ability of the downstream section of coil to provide adequate superheat.

Row-split coils are generally not recommended for comfort-cooling applications. When applied, they require careful coil selection, expansion valve sizing and selection, and control.

Shell-and-Tube Evaporator Control

shell-and-tube evaporator

refrigerant vapor

liquid

refrigerant expansion valve

Figure 37

The capacity of a shell-and-tube evaporator is primarily controlled by the unloading or cycling of compressors. However, as with a finned-tube evaporator, it also uses an expansion valve to control the flow rate of refrigerant through the evaporator and ensure the proper amount of superheat in the system.

Ashell-and-tube evaporator may also contain more than one liquid refrigerant circuit, each served by one expansion valve.

TRG-TRC005-EN

25

Page 32
Image 32
Trane trg-trc005-en manual Shell-and-Tube Evaporator Control