Installation and Service
All Installation and service must be performed by qualified service personnel.
Read and follow all warning notices and instructions marked on the product or included in the manual.
Required Grounding
This product is intended to be used in a restricted access location Connect the device to a 48 VDC SELV (Safety Extra Low Voltage) supply that is electrically isolated from the DC Source. The 48 VDC source is to be reliably connected to earth (ground). Equipment grounding is vital to ensure safe operation.
Prior to installation, use a voltmeter/ohmmeter to check the wiring for the presence of earth ground.
Required Disconnect
A readily accessible disconnect device as part of the building installation shall be incorporated into the fixed wiring. The disconnect device (a 48 VDC, 15 or 20A circuit breaker or switch) must be included in the ungrounded supply conductor.
Installation -- Continued
SPS-1872-SA (Stand Alone)
NOTE: The
1.Place on any
2.Connect the barrel connector on the
SPS-1872-CC / SPS-1872-PS / SPS-1872-DPS
The
Note the differences between the three devices below:
Overcurrent protection must be a 15 or 20A, 48 VDC fuse or circuit breaker.
CAUTION: Ensure that the power source is NOT powered when connecting it to the
CAUTION: Wear a grounding device and observe electrostatic discharge precautions when installing or servicing the power supply module. Failure to observe this caution could result in damage to, and subsequent failure of, the power supply module.
WARNING: The SPS1872 must be attached to a limited current circuit with a
3.125 in.
3.375 in.
3.375 in.
The
Note that this device is slightly narrower than the other two devices.
The
The
Note that this device is taller than the other two devices.