Trion SPECIFICATIONS FM 1000 Electrostatic, FM 1000 Media, FM 1000 E ELECTROSTATIC, Operation

Models: FM 1000

1 15
Download 15 pages 19.47 Kb
Page 2
Image 2
SPECIFICATIONS

SPECIFICATIONS

FM 1000 Electrostatic

Input Voltage:

120 V, 60 HZ, 1 PH

Amp Draw:

3.1 Max.

Unit Weight:

108 lbs.

Air Output:

600, 800 and 1100 CFM (nominal)

Options:

1.

Charcoal After Filter

 

2.

Remote Discharge

 

FM 1000 Media

Input Voltage:

120 V, 60 HZ, 1 PH

Amp Draw:

4.0 Max

Unit Weight:

88 lbs.

Air Output:

400, 500 and 650 CFM (nominal)

Options:

1.

Charcoal After Filter

 

2.

Remote Discharge

This manual provides information for location, installation, operation and service of the FM 1000 E & M. Before installation and use of the air cleaner, carefully read these instructions to insure maximum benefits from the unit and to avoid needless service cost that result from improper installation.

FM 1000 E ELECTROSTATIC

The FM 1000 E electronic air cleaner is technically known as a two-stage electrostatic precipitator. It is designed to remove airborne particles, dust, dirt, smoke or other indoor air pollutants.

Air movement through the unit is controlled by its own blower system. As dirty air enters the unit, it passes through a pre-filter, which removes large particles by direct impingement.

The pre-filtered air then passes through a two-stage electrostatic precipitator. In the first stage of electrical operation, all airborne particles, even of submicroscopic size are electrically charged (positive) as they pass through the ionizer. In the second stage of operation, the charged particles pass into an electrical field established between a series of parallel plates, forming the negative element of the field established between a series of parallel plates that collect airborne particulate.

FM 1000M MEDIA FILTER

The FM 1000M with media filtration instead of an Ionizer/Collector cell utilizes the same type pre-filter but a mechanical media or fabric main filter to trap airborne pollutants in the filter fibers. As more pollutants are collected, the efficiency of the media filter is increased to a point where air delivery from the unit is reduced and effective air cleaning does not take place. It is then time

to change the filter and wash the pre-filter. (From 1 to 4 months, depending on the application).

The media main filter and charcoal after-filter are disposable when dirty. Replace with new filters from your authorized Trion Representative.

OPERATION

CONTROL SWITCH

The 3 position control switch located on the exposed side of the installed unit, controls the operation of the power supply and the speed of the fan: Low, Medium or High. (Power Supply not needed on FM 1000 Media Unit).

LED LIGHTS (Red not used on FM 1000M)

The green LED indicates the unit has electrical power and the switch has been turned to one of the 3 positions.

The Red LED indicates High Voltage (approximately 6800 VDC) is supplied to the Ionizer / Collector cell. (Red not used on Media unit).

FILTER ACCESS

The filter access screws located on the access door of the unit hold the access door closed, and are designed to automatically disconnect electrical power when the access door is opened (Item 6, Page 5). The access door may be removed for convenience of unit installation and cleaning once in operation.

INSTALLATION

Read instructions carefully before beginning installation.

CAUTION:

ELECTRONIC AIR CLEANERS CANNOT BE USED IN AREAS WHERE COMBUSTIBLE GASES OR VAPORS

ARE PRESENT. USE GLOVES DURING INSTALLATION TO PREVENT POSSIBLE INJURY FROM EXPOSED METAL.

T-BAR CEILING INSTALLATION

DO NOT INSTALL THE UNIT IN A T-BAR CEILING UNLESS THE UNIT CAN BE SECURED TO THE PERMANENT CEILING OR CEILING JOIST, BEAMS, ETC. AS DESCRIBED HEREIN.

1.Installer must provide the 2/0 chain or other hanger material as required.

2.Carefully unpack the unit and check for damage incurred in shipment. Report any damage to the freight carrier and your TRION Representative immediately.

2

Page 2
Image 2
Trion SPECIFICATIONS FM 1000 Electrostatic, FM 1000 Media, FM 1000 E ELECTROSTATIC, FM 1000M MEDIA FILTER, Operation