LCD DISPLAY SELECT SWITCH

Operation (Normal Conditions) (continued)

LCD DISPLAY SELECT SWITCH

Momentarily press the “SELECT” switch on the front panel to browse through different power readings on the LCD Display. The LCD Display will show which one of four operational modes your UPS is currently in: Normal, Economy, On-Battery, or Bypass. Also, as you press the “SELECT” switch, the LCD Display will browse through load, input, bypass, output and battery conditions.

"NORMAL" MODE OPERATION "ON-BATTERY" MODE OPERATION

ON INVERTER

LOAD = XXX% X.XXKW

PRESS SELECT KEY

ON INVERTER

IN R = XXXV XX.XHz

PRESS SELECT KEY

ON INVERTER

IN S = XXXV T=XXXV

PRESS SELECT KEY

ON INVERTER

OUT = XXXV XX.XHz

PRESS SELECT KEY

ON INVERTER

BATT = XXXV XXX%

PRESS SELECT KEY

ON BATTERY

LOAD = XXX% X.XXKW

PRESS SELECT KEY

ON BATTERY

IN R = XXXV XX.XHz

PRESS SELECT KEY

ON BATTERY

IN S = XXXV T=XXXV

PRESS SELECT KEY

ON BATTERY

OUT = XXXV XX.XHz

PRESS SELECT KEY

ON BATTERY

BATT = XXXV XXX%

PRESS SELECT KEY

"ECONOMY" MODE OPERATION "ON BYPASS" MODE OPERATION

ECONOMY MODE

LOAD = XXX% X.XXKW

PRESS SELECT KEY

ECONOMY MODE

IN R = XXXV XX.XHz

PRESS SELECT KEY

ECONOMY MODE

IN S = XXXV T=XXXV

PRESS SELECT KEY

ECONOMY MODE

OUT = XXXV XX.XHz

PRESS SELECT KEY

ECONOMY MODE

BATT = XXXV XXX%

PRESS SELECT KEY

ON BYPASS

LOAD = XXX% X.XXKW

PRESS SELECT KEY

ON BYPASS

BYPS = XXXV XX.XHz

PRESS SELECT KEY

ON BYPASS

OUT = XXXV XXX%

PRESS SELECT KEY

Operation (Special Conditions)

OPERATION ON BYPASS—VOLTAGE OUT OF RANGE

While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.

Bypass Voltage Condition

LCD Display Message

 

 

>15% Higher than Nominal

BYPASS HI NO O/P

 

 

>20% Lower than Nominal

BYPASS LO NO O/P

 

 

Was Too High, Now Nominal

BYPASS WAS HI

 

 

Was Too Low, Now Nominal

BYPASS WAS LO

 

 