8 millisecond automatic transfer between line and battery power supports UPS protection during blackouts and voltage fluctuations for nearly all computer and networking applications
2400 watts continuous AC output in inverter mode, 2400 watts continuous AC output in AC mode
Double Boost™ inverter output supports momentary startup loads up to 200% of the continuous rating for up to 10 seconds OverPower™ inverter output supports longer duration overloads to 150% for
3 stage, 15 amp battery charger with adjustable settings for wet/gel battery types offers fast, reliable battery recharging
Protected hardwire
Protected hardwire output passes 120V line power or inverter output through to connected equipment
Reliability enhanced
3 position operating mode switch supports "AUTO" mode to enable automatic transfer between DC and AC modes,
Set of six front panel LEDs display AC/DC operational modes, overload status, DC voltage level, shutdown status and system fault status Set of 4 configuration dipswitches support wet/gel battery charging profiles, adjustable 135/145V high voltage auto transfer during overvoltages and selectable 75/85/95/105V AC low voltage auto transfer during brownouts
Set of 4 additional configuration dipswitches support 4 levels of charger limiting relative to output load size, a battery equalization program and battery charger on / off settings
Resettable 15A charger AC input breaker and resettable 20A AC output breaker and automatic 2 speed cooling fan protect the inverter from load and temperature related failures
Grounding lug properly connects the inverter/charger system to earth ground or vehicle grounding system
Automatic overload and thermal shutoff safely turns off inverter as excessive loads or overheating conditions develop
Front panel remote control connector enables remote off/on switching (requires APSRM4 switch accessory). Optional APSRM4 accessory also includes user configurable jacks to support inverter shutoff or startup as a vehicle ignition is engaged
Load sensing control dial enables adjustable load threshold required to automatically turn the inverter on and off in DC mode as load conditions change
Specifications
OVERVIEW
Intended | Emergency Home Power |
Application |
|
|
|
SYSTEM OVERVIEW |
|
Voltage | 48VDC / 120VAC |
compatibility |
|
|
|
Frequency | 60 Hz |
compatibility |
|
|
|
OUTPUT |
|
Output watts | 2400W (continuous) / 4800W (peak) |
|
|
Output nominal | 120V |
voltage |
|
|
|
Output voltage | LINE POWER (AC): Maintains 120V nominal sine wave output from line power source. INVERTER POWER (AC): |
regulation | Maintains PWM sine wave output voltage of 120 V AC |
|
|
Output frequency | 60 Hz (+/- 0.3 Hz) |
regulation |
|
|
|
Outlet quantity / | Hardwire |
type |
|
|
|
Overload | Includes 15A input breaker dedicated to the charging system and 20A output breaker for AC output loads. |
protection |
|
|
|
Continuous output | 2400 |
capacity (watts) |
|
|
|
Peak output | 4800 |
capacity (watts) |
|
|
|
INPUT |
|
Input connection | DC INPUT: Set of 2 DC |
type |
|
|
|