Alarms
Switches
Audible alarms for ON BATTERY, LOW BATTERY and OVERLOAD status
Main power switch controls ON, OFF,
SURGE / NOISE SUPPRESSION
AC surge suppression | 420 joules |
|
|
AC suppression | Instantaneous |
response time |
|
|
|
Dataline suppression | Single line TEL/DSL |
|
|
EMI / RFI AC noise | > 40dB@1MHz |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 10.1 |
|
|
Shipping weight (kg) | 4.6 |
|
|
Shipping Dimensions | 4.6 x 15.04 x 9.84 |
(HWD/in) |
|
|
|
Shipping Dimensions | 11.7 x 38.2 x 25 |
(HWD/cm) |
|
|
|
Unit weight (lbs) | 8.8 |
|
|
Unit weight (kg) | 4 |
|
|
Unit Dimensions | 3.07 x 12.22 x 6.91 |
(HWD/in) |
|
|
|
Unit Dimensions | 7.8 x 31 x 17.5 |
(HWD/cm) |
|
|
|
Material of | ABS |
construction |
|
|
|
Form factors | Tower, Desktop, |
supported |
|
|
|
Integrated keyhole | Keyhole mounting slots enable |
mounting tabs |
|
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|
Storage Temperature | +5 to +122 degrees Fahrenheit / |
|
|
Operating | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Temperature |
|
|
|
Line mode BTU/hr. | 4 BTU/Hr. / 99% line power efficiency (fully charged battery) |
(Max.) |
|
|
|
COMMUNICATIONS |
|
Network monitoring | USB (HID Compliant) |
port |
|
|
|
Software and cabling | Includes USB interface cable, PowerAlert software available via free download |
included |
|
|
|
WatchDog | Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft |
compatibility | reboot of application / OS or hard power off/on reboot of connected equipment - ideal for unattended kiosk applications |
|
|
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode
AC to battery mode: 6 milliseconds / Battery to AC mode: 3 milliseconds
Low voltage transfer to battery power
High voltage transfer to battery power
Switches to battery power as line voltage decreases to 99 volts or less. Resets back to line power mode as line voltage increases to 104V or higher
Switches to battery power as line voltage increases to 139V or higher. Resets back to line power mode when line voltage decerases to 135V or lower