6.Diagrams (continued)
6.3Integrated Battery Charger (Select Models)
6.25 MAX
0.5
13.5
12.5
Input Voltage Selection
For 120 VAC Jumper:
2 & 3, 3 & 4, 5 & 6
For 208 VAC Jumper:
1 & 2, 4 & 5
For 240 VAC Jumper:
2 & 3, 4 & 5
AC | L N | - | + | |
Input |
|
|
| |
|
| 120 VAC | Output | |
|
| |||
|
| Output |
|
|
|
|
|
|
|
Warning: Do not connect the battery charger AC input to the UPS system output. The battery charger requires a separate AC supply circuit.
Notes:
•All dimensions are in inches.
•AC input is preset with fuses for 120V 30 A, but can be rewired for 208 and 240 VAC, 60 Hz by a qualified electrician.
•Constant voltage output.
•Electronic current limiting and high voltage shutdown.
•Temperature compensation with remote battery temperature sensor.
•Auxiliary output circuit for “Charger OK” indicator.
13