Battery recharge rate

Replacement Battery Cartridge

2-4 hours to 90%

RBC53

VOLTAGE REGULATION

Voltage regulation description

Overvoltage correction

Direct pass through

Brownout correction

Severe brownout correction

Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using battery power, during brownouts to 75V and overvoltages to 147V

Input voltages between 128 and 147V AC are reduced by 12%

Input voltages between 108 and 127V AC are passed on to connected equipment unchanged

Input voltages between 93 and 107V AC are boosted by 14%

Input voltages between 75 and 92V AC are boosted by 30%

LEDS ALARMS & SWITCHES

Front panel LEDs

Alarms

Switches

Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information

Audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) and low battery (continuous tone)

Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions

SURGE / NOISE SUPPRESSION

AC surge

480 joules

suppression

 

 

 

AC suppression

Instantaneous

response time

 

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight (lbs)

42.6

 

 

Shipping weight (kg)

19.4

 

 

Unit weight (lbs)

38.4

 

 

Unit weight (kg)

17.5

 

 

Unit Dimensions

12.75 x 7.5 x 9

(HWD/in)

 

 

 

Unit Dimensions

32.4 x 19.1 x 22.9

(HWD/cm)

 

 

 

Material of

PVC

construction

 

 

 

Form factors

Tower

supported

 

 

 

Cooling method

Built-in rear exit cooling fan

 

 

Battery Access

Battery access door allows hot swap battery replacement without powering connected equipment off

 

 

ENVIRONMENTAL

 

Relative Humidity

0 to 95%, non-condensing

 

 

Storage Temperature

+5 to +122 degrees Fahrenheit

 

 

Operating

+32 to +104 degrees Fahrenheit

Temperature

 

 

 

COMMUNICATIONS

 

Network monitoring

1-USB & 1-DB9

port

 

 

 

Software and cabling

Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Ships with 2

included

cables, 1-USB to USB & 1-DB9 to DB9

 

 

Page 3
Image 3
Tripp Lite SM1500NAFTA Voltage Regulation, Leds Alarms & Switches, Surge / Noise Suppression, Physical, Environmental