Includes 6 fully protected NEMA 5-15R outlets with 2 single outlet load banks that can be individually powered off and back on again via software interface

PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification, event logging and running user defined script commands

Offers simultaneous monitoring of up to 3 directly connected devices through included DB9 contact closure and RS-232 enabled interfaces, or the monitoring of any number of additional servers over IP with included PowerAlert monitoring software

In addition to the contact closure monitoring of on battery, low battery and power restored messaging, built-in RS-232 interface supports messaging of UPS and line power status, including AC line voltage, DC battery voltage and remaining battery capacity

Supports activate self-test and UPS output power control for delayed or immediate reboot of connected equipment

Diagnostic LEDs (indicate 17 performance conditions)

UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Business) Listed $250,000 Ultimate Lifetime Insurance (USA & Canada Only)

Specifications

SYSTEM OVERVIEW

Voltage compatibility

120V AC

 

 

Frequency

60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

2200

 

 

Output watts

1700

 

 

Output nominal

120V AC

voltage

 

 

 

Output voltage

LINE MODE: Sine wave line voltage 120V (-13% / +5%)

regulation

BATTERY MODE: PWM sine wave output 120V +/-5%

 

 

Output frequency

LINE MODE: Passes line frequency of 60Hz +/-10%

regulation

BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz

 

 

Outlet quantity / type

6 NEMA 5-15R

 

 

Customized load

2 individually controlled single-outlet banks supports reboot of selected items and load shedding to increase battery

management

runtime for the most critical of loads.

receptacles

 

 

 

Overload protection

Via 20A input breaker

 

 

INPUT

 

Maximum input amps

15A, 1770 watts

 

 

Input connection type

NEMA 5-15P

 

 

Input cord length

8 ft., 12 gauge

 

 

Recommended

20A 120V

Electrical Service

 

 

 

BATTERY

 

Full load runtime

11 minutes (2200VA)

 

 

Half load runtime

27 minutes (1100VA)

 

 

Expandable battery

Supports extended runtime with optional BP24V28-2U (limit 1) and BP24V70-3U (multi-pack compatible). Capacity

runtime

de-rates to 1600VA / 1280 watts with 1 external battery pack and 1250VA / 800 watts with any 2 external battery packs

 

 

DC system voltage

24 V DC

 

 

Typical battery

3-6 years, depending on usage

lifespan

 

 

 

Battery recharge rate

2-4 hours to 90%

VOLTAGE REGULATION

Voltage regulation description

Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to maintain usable, computer grade output without consuming battery power.

Page 2
Image 2
Tripp Lite SM2200NAFTA warranty Specifications