Full load runtime
Half load runtime
DC system voltage
Typical battery lifespan
Battery recharge rate
Replacement Battery Cartridge
3 minutes (500VA)
8 minutes (250VA)
12 VDC
VOLTAGE REGULATION
Voltage regulation description
Brownout correction
Line interactive voltage regulation system corrects brownouts as low as 90 volts back to usable 120V nominal levels
Input voltages between 90 and 108 are boosted by 14%
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
5 front panel LEDs - green POWER LED, green AVR LED,
Audible alarm warns of power failure, overload, UPS fault and low battery conditions
Includes 2 front panel mounted
SURGE / NOISE SUPPRESSION
AC surge | 480 joules |
suppression |
|
|
|
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 19.9 |
|
|
Shipping weight (kg) | 9 |
|
|
Shipping | 5 x 22.5 x 16 |
Dimensions (HWD/in) |
|
|
|
Shipping | 12.7 x 57.2 x 40.6 |
Dimensions |
|
(HWD/cm) |
|
|
|
Unit weight (lbs) | 17.6 |
|
|
Unit weight (kg) | 8 |
|
|
Unit Dimensions | 1.75 x 17.5 x 11.75 |
(HWD/in) |
|
|
|
Unit Dimensions | 4.45 x 44.5 x 29.8 |
(HWD/cm) |
|
|
|
Material of | Steel |
construction |
|
|
|
Form factors | Rack (1U) |
supported |
|
|
|
Battery Access | Battery access door allows hot swap battery replacement without powering connected equipment off |
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|
Storage Temperature | +5 to +122 degrees Fahrenheit / |
|
|
Operating | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Temperature |
|
|
|