Expandable battery runtime
DC system voltage
Typical battery lifespan
Battery recharge rate
Replacement Battery Cartridge
Runtime is expandable with
36VDC
RBC53
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Direct pass through
Brownout correction
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated
Input voltages between 132 and 145V AC are reduced by 13%
Input voltages between 106 and 131V AC are passed on to connected equipment unchanged
Input voltages between 91 and 105 V AC are boosted by 17%
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
Includes 14 front panel LEDs to indicate line / battery power status, over / under voltage correction, battery charge level (4 LEDs), load percentage (4 LEDs), overload and replace battery. Also includes 1 rear panel site wiring fault indicator.
Audible alarms indicate BATTERY MODE (.4 sec. On / 4.6 sec. Off) and OVERLOAD (.4 sec. On / .6 sec. Off), UPS POWERED ON (single .4 sec. On)
Yes, includes 2 front panel mounted switches - POWER ON switch powers UPS on in AC or battery mode when pressed longer than one second. Power on switch also initiates self test when pressed longer than .5 seconds as the UPS is in line power mode. Also ser
SURGE / NOISE SUPPRESSION
AC surge | 480 joules |
suppression |
|
|
|
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 50 |
|
|
Shipping weight (kg) | 22.7 |
|
|
Shipping | 13 x 10 x 23.75 |
Dimensions (HWD/in) |
|
|
|
Shipping | 33 x 25.4 x 60.3 |
Dimensions |
|
(HWD/cm) |
|
|
|
Unit weight (lbs)
Unit weight (kg)
Unit Dimensions (HWD/in)
Unit Dimensions (HWD/cm)
Material of construction
Form factors supported
Cooling method
Battery Access
ENVIRONMENTAL
45.5
20.7
8.75x 6.75 x 16.75
22.2x 17.2 x 42.5
Steel
Tower
Fan
Supports battery access and