Customized load management receptacles
3 individually controllable single outlet
Overload protection | Via 40A input circuit breaker |
|
|
INPUT |
|
Maximum input | 24A with |
amps |
|
|
|
Input connection | |
type |
|
|
|
Input cord length | 10 ft. |
|
|
Recommended | 120V 30A |
Electrical Service |
|
|
|
BATTERY |
|
Full load runtime | With |
|
|
Half load runtime | With |
|
|
DC system voltage | 48VDC |
|
|
Replacement | RBC54 (qty 2) |
Battery Cartridge |
|
|
|
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Brownout correction
Severe brownout correction
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated
Input voltages between 127 and 145V AC are reduced by 12%
Input voltages between 96 and 108V AC are boosted by 12%
120V only: Input voltages between 83 and 95 are boosted by 24%
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
5 front panel LEDs - Green POWER LED, Green VOLTAGE CORRECTION LED, 3 color BATTERY CHARGE LED, 3 color OUTPUT LOAD LEVEL LED, red BATTERY WARNING LED.
3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) and low battery (continuous tone)
Yes, includes 2 front panel mounted
SURGE / NOISE SUPPRESSION
AC surge | 570 joules |
suppression |
|
|
|
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight | 124 |
(lbs) |
|
|
|
Shipping weight (kg) | 56.3 |
|
|
Shipping | 13.2 x 23.6 x 22.8 |
Dimensions |
|
(HWD/in) |
|
|
|
Shipping Dimensions (HWD/cm)
33.5 x 59.9 x 57.9
Unit weight (lbs)
102
Unit weight (kg)
46.3