Tripp Lite SMART750RM1U warranty Specifications, System Overview, Output, Input, Battery

Models: SMART750RM1U

1 5
Download 5 pages 34.52 Kb
Page 2
Image 2
Specifications

SYSTEM OVERVIEW Network interfaces support simultaneous communications via USB, DB9 serial and SNMPWEBCARD slot

OUTPUT Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP

INPUT Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, internal UPS temperature, AC line frequency, timed inverter shutoff, activate self-test and load bank output power control

BATTERY Built in Emergency Power Off (EPO) interface with cable

Manual background Sine wave output in AC and battery modes

Manual background Half load runtime of 24 minutes (375VA/225 watts)/Full load runtime of 7 minutes (750VA/450 watts)

Manual background Includes 6 NEMA 5-15R output receptacles arranged in 2 switchable single-outlet load banks

Manual background Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual devices

Manual background 3 stage metered LEDs offer current monitoring and battery charge level

Manual background Mains power and voltage regulation LEDs offer at-a-glance power status information

Manual background Front panel switches support self-test and alarm cancel functions

Manual background UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required

Manual background UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Emissions) listed

Manual background 2 year manufacturer's product warranty, $250,000 Ultimate Lifetime Insurance

Specifications

SYSTEM OVERVIEW

Voltage compatibility

120 VAC

 

 

Frequency

60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

750

 

 

Output watts

450

 

 

Output nominal

120V AC

voltage

 

 

 

Output voltage

LINE MODE: Sine wave line voltage 120V (-21% +8%), BATTERY MODE: Sine wave output within 5% of 120VAC

regulation

 

 

 

Output frequency

LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz

regulation

 

 

 

Outlet quantity / type

6 NEMA 5-15R

 

 

Customized load

Includes 2 single-outlet load banks that support load shedding and remote reboot on demand of locked network

management

devices. Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for

receptacles

servers and other critical devices.

 

 

Overload protection

15A input breaker

 

 

INPUT

 

Maximum input amps

7A

 

 

Input connection

NEMA 5-15P

type

 

 

 

Input cord length

10 ft., 14 gauge

 

 

Recommended

15A 120V

Electrical Service

 

 

 

BATTERY

 

Full load runtime

7 minutes (450 watts)

 

 

Half load runtime

24 minutes (225 watts)

 

 

DC system voltage

24 VDC

 

 

Typical battery

3-6 years, depending on usage

lifespan

 

 

 

Battery recharge rate

2-4 hours to 90%

Page 2
Image 2
Tripp Lite SMART750RM1U warranty Specifications, System Overview, Output, Input, Battery