Outlet quantity / type

Customized load management receptacles

6 NEMA 5-15R

2 single outlet controllable load banks support load shedding and remote reboot on demand of locked network devices.

Overload

15A input breaker

protection

 

 

 

INPUT

 

Maximum input

8.6A

amps

 

 

 

Input connection

NEMA 5-15P

type

 

 

 

Input cord length

10 ft. 14 gauge

 

 

Recommended

15A 120V

Electrical Service

 

 

 

BATTERY

 

Full load runtime

4.5 minutes with internal batteries (800 watts)

 

 

Half load runtime

14 minutes with internal batteries (400 watts)

 

 

Expandable

Supports extended runtime with optional external battery packs BP24V15RT2U (limit 1), BP24V28-2U (limit 1) and

battery runtime

BP24V70-3U (multi-pack compatible)

 

 

DC system voltage

24VDC

 

 

Typical battery

3-6 years, depending on usage

lifespan

 

 

 

Battery recharge

Less than 6 hours to 80%

rate

 

 

 

Replacement

RBC92-2U

Battery Cartridge

 

 

 

VOLTAGE REGULATION

Voltage regulation description

Overvoltage correction

Brownout correction

On-line, double-conversion power conditioning maintains output within 2% of 100/110/120 volts at all times

Maintains output of selected nominal +/-2% during overvoltages to 138V AC

Maintains output of selected nominal +/-2% during undervoltages to 65V AC (at loads greater than 70% undervoltage correction extends to 80V)

LEDS ALARMS & SWITCHES

Front panel LEDs

LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red), battery low (yellow) - 4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%). LED display panel easily rotates for better viewing in rackmount or tower configurations.

Alarms

Multi-function audible alarm with distinctive ring patterns offer notification of backup operation (2 seconds on / 0.5 seconds off), low battery warning (1.25 seconds on / 0.5 seconds off), overload (sounds continuously), UPS fault (4.2 seconds on / 1 second off), input voltage out of frequency (2.1 seconds on / 0.14 seconds off) and high input voltage (2.1 seconds on 0.07 seconds off)

Switches

Includes power off/on switch to enable system turn on (press ON switch), UPS battery test (press ON switch during normal AC operation), buzzer silence (press ON switch during battery operation) and OFF (press OFF switch) - all switch functions require that the switch be pressed and held for longer than 2 seconds, but less than 4 seconds

SURGE / NOISE SUPPRESSION

AC surge suppression

AC suppression response time

Dataline suppression

480joules

Instantaneous

Set of 8 wire RJ style interface jacks offer surge suppression for network ethernet or TEL/DSL connection. Pins 1,2,3 and 6 offer ethernet protection starting at 7.5V and the center two wires, pins 4 & 5, offer TEL/DSL line suppression starting at 260V

Page 3
Image 3