Shipping weight (lbs)
Shipping weight (kg)
Shipping Dimensions (HWD/in)
57.3
26
9.75 x 20.25 x 24
Shipping Dimensions (HWD/cm)
24.8 x 51.4 x 61
Unit weight (lbs) | 47.4 |
|
|
Unit weight (kg) | 21.5 |
|
|
Unit Dimensions | 3.5 x 17.5 x 19 |
(HWD/in) |
|
|
|
Unit Dimensions | 8.9 x 44.4 x 48.3 |
(HWD/cm) |
|
|
|
Material of | Steel |
construction |
|
|
|
Form factors | Rack (2U) |
supported |
|
|
|
Cooling method | |
|
|
Battery Access | User replaceable, hot swap battery replacement supported via front access panel |
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|
Storage | +5 to +122 degrees Fahrenheit / |
Temperature |
|
|
|
Operating | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Temperature |
|
|
|
Line mode BTU/hr. | 812.9 BTU/hr. (worst case) |
(Max.) |
|
|
|
Battery mode | 885.6 BTU/hr. (worst case) |
BTU/hr. (Max.) |
|
|
|
COMMUNICATIONS |
|
Network | Includes USB and DB9 serial ports. |
monitoring port | closure monitoring ability. |
| shutdown features of Windows and Mac OS X. |
|
|
Software and | Yes, includes PowerAlert software |
cabling included |
|
|
|
SNMP compatibility | Yes, includes slot for optional SNMPWEBCARD accessory (#SNMPWEBCARD) |
|
|
WatchDog | Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot |
compatibility | of application / OS or hard power off/on reboot of connected equipmentideal for unattended kiosk applications |
|
|
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode
Low voltage transfer to battery power
Zero, online UPS continuously converts incoming AC to DC, then back to AC. When commercial power is interrupted, UPS maintains continuous output from battery reserves with absolutely no disruption in output AC power.
Maintains continuous operation during undervoltages as low as 65V (80V at load levels over 70%). Below this switchover point, output is supported from battery derived AC power.
High voltage | Maintains continuous operation without using battery power during overvoltages to 138V. Above this point, output is |
transfer to battery | supported from battery derived AC power. |
power |
|
|
|
SPECIAL FEATURES |
|
EPO port | Supports "Emergency Power Off" via dedicated |
|
|