True
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types
Corrects line voltage conditions as low as 65V and as high as 138V back to selectable 110/120V
Standard internal battery set offers 14 minutes runtime at half load (800W) and 4.5 minutes at full load (1600W)
Optional
Space saving upright tower format
Fault tolerant
Network interfaces support simultaneous communications via
HID compliant USB interface enables integration with
UPS interface supports
NEMA
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required
Single line TEL/DSL or network ethernet line surge suppression
2 year manufacturer's product warranty, $250,000 Ultimate Lifetime Insurance
Specifications
SYSTEM OVERVIEW
Voltage | 120V AC (110/120V) |
compatibility |
|
|
|
Frequency | 50/60 Hz compatible |
compatibility |
|
|
|
OUTPUT |
|
Output VA | 2200 |
|
|
Output watts | 1600 |
|
|
Output nominal | 120V AC (110/120V) |
voltage |
|
|
|
Output voltage | Maintains |
regulation | 5% total harmonic distortion (computer load) (Less than 5% THD |
|
|
Output frequency | Regulates line frequency to 50/60Hz +/- 0.05Hz |
regulation |
|
|
|
Outlet quantity / | 6 NEMA |
type |
|
|
|
Customized load | 2 controllable load banks support load shedding and remote reboot on demand of locked network devices (3 outlets per |
management | load bank) |
receptacles |
|
|
|
Overload | Via 30A input breaker |
protection |
|
|
|
INPUT |
|
Maximum input | 16A (120V) / 17.6 (110V) |
amps |
|
|
|
Input connection | NEMA |
type |
|
|
|
Input cord length
10ft / 3m