Specifications

SYSTEM OVERVIEW Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems

OUTPUT Accepts input voltages between 160 and 275 (130 to 275 at loads under 70%), regulating output to selectable 200/208/220/230/240V +/-2%

INPUT 3000VA/2400 watt power capacity with 8 total outlets (6 NEMA6-15/20R & 2 NEMAL6-20R)

BATTERY Standard internal battery set provides 14 minutes runtime at half load

Manual background Expandable runtime with multiple external battery packs (part# BP72V15-2U limit 1/BP72V28-3U multi-pack compatible)

Manual background Innovative design makes unit adaptable for rackmount, tower, or stacking applications

Manual background Uses only 3 rack spaces (3U) in standard 19 inch rack

Manual background DB9 serial port for network interface; SNMP compatible

Manual background Slot for optional SNMP/web card (part# SNMPWEBCARD)

Manual background PowerAlert unattended shutdown software and 6 ft. network cable included

Manual background Compatible with Tripp Lite's Watchdog Service Monitoring/Reboot Software

Manual background Fault tolerant auto-bypass maintians continuous utility output to connected equipment, even in cases where the UPS is overloaded or suffers an internal failure that requires service

Manual background Diagnostic LEDs

Manual background Battery replacement door

Manual background Mounting hardware included for 4 post rack enclosures, 2 post telecom rack compatible with separate purchase 2POSTRMKITWM accessory

Manual background $250,000 Ultimate Lifetime connected equipment insurance Manual background 2 year manufacturer's product warranty

Specifications

SYSTEM OVERVIEW

Voltage

208V AC

compatibility

 

 

 

Frequency

50/60 Hz compatible

compatibility

 

 

 

OUTPUT

 

Output VA

3000

 

 

Output watts

2400

 

 

Output nominal

208V AC (200/220/230/240V)

voltage

 

 

 

Output voltage

Maintains full-time sine wave output within 2% of selected nominal voltage, less than 5% total harmonic distortion

regulation

 

 

 

Output frequency

Regulates line frequency to 50/60Hz +/- 0.05Hz

regulation

 

 

 

Outlet quantity /

6 NEMA 6-15/20R, 2 NEMA L6-20R

type

 

 

 

Customized load

2 individually controllable load banks support load shedding and remote reboot on demand of locked network devices.

management

Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for servers

receptacles

and other critical devices. (Bank A consists of 4 outlets / Bank B consists of 2 outlets)

 

 

Overload protection

Via 25A input breaker

 

 

INPUT

 

Maximum input

14.9 / 14.3 / 13.1 / 12.6 / 12.1 Amps (depending on voltage) / 2844 watts

amps

 

 

 

Input connection

NEMA L6-20P

type

 

 

 

Input cord length

10 ft. 14 gauge

 

 

Recommended

15A 200-240V

Electrical Service

 

 

 

BATTERY

 

Full load runtime

Internal batteries — 5 min. (3000VA)

 

 

Half load runtime

Internal batteries — 14 min. (1500VA)