Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems
Accepts input voltages between 160 and 275 (130 to 275 at loads under 70%), regulating output to selectable 200/208/220/230/240V
3000VA/2400 watt power capacity with 8 total outlets (6
Standard internal battery set provides 14 minutes runtime at half load
Expandable runtime with multiple external battery packs (part#
Innovative design makes unit adaptable for rackmount, tower, or stacking applications
Uses only 3 rack spaces (3U) in standard 19 inch rack
DB9 serial port for network interface; SNMP compatible
Slot for optional SNMP/web card (part# SNMPWEBCARD)
PowerAlert unattended shutdown software and 6 ft. network cable included
Compatible with Tripp Lite's Watchdog Service Monitoring/Reboot Software
Fault tolerant
Diagnostic LEDs
Battery replacement door
Mounting hardware included for 4 post rack enclosures, 2 post telecom rack compatible with separate purchase 2POSTRMKITWM accessory
$250,000 Ultimate Lifetime connected equipment insurance 2 year manufacturer's product warranty
Specifications
SYSTEM OVERVIEW
Voltage | 208V AC |
compatibility |
|
|
|
Frequency | 50/60 Hz compatible |
compatibility |
|
|
|
OUTPUT |
|
Output VA | 3000 |
|
|
Output watts | 2400 |
|
|
Output nominal | 208V AC (200/220/230/240V) |
voltage |
|
|
|
Output voltage | Maintains |
regulation |
|
|
|
Output frequency | Regulates line frequency to 50/60Hz +/- 0.05Hz |
regulation |
|
|
|
Outlet quantity / | 6 NEMA |
type |
|
|
|
Customized load | 2 individually controllable load banks support load shedding and remote reboot on demand of locked network devices. |
management | Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for servers |
receptacles | and other critical devices. (Bank A consists of 4 outlets / Bank B consists of 2 outlets) |
|
|
Overload protection | Via 25A input breaker |
|
|
INPUT |
|
Maximum input | 14.9 / 14.3 / 13.1 / 12.6 / 12.1 Amps (depending on voltage) / 2844 watts |
amps |
|
|
|
Input connection | NEMA |
type |
|
|
|
Input cord length | 10 ft. 14 gauge |
|
|
Recommended | 15A |
Electrical Service |
|
|
|
BATTERY |
|
Full load runtime | Internal batteries — 5 min. (3000VA) |
|
|
Half load runtime
Internal batteries — 14 min. (1500VA)