4 post installation hardware included, Optional 2POSTRMKITHD enables 2 post rack installation

Single line TEL / Network surge suppression

Electronic bypass maintains utility output during a variety of UPS fault conditions

Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement

Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60 to 50Hz

Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options

HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software

Specifications

OUTPUT

Output Volt Amp Capacity (VA)

Output kVA capacity (kVA)

Output Watt Capacity (watts)

Output kW capacity

Output power factor

Output Capacity Details

3000

3

2700

2.7

0.9

ON LINE MODE: Maximum output capacity ratings are reduced for some nominal voltage settings (127/120V 2700 watts / 115V 2430 watts / 110V 2295 watts / 100V 2160 watts). FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion mode (127/120V 1890 watts / 115V 1701 watts / 110V 1606 watts / 100V 1512 watts).

Crest Factor

Nominal Output

Voltage(s)

Supported

3:1

100V; 110V; 115V; 120V; 127V

Nominal Voltage details

Frequency compatibility

Frequency compatibility details

120V factory-default nominal voltage

50/60 Hz (auto-selectable); Supports 50 to 60 Hz and 60 to 50 Hz conversion

ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is regulated to +/-0.05Hz.

Output voltage regulation (line mode)

+/- 2%

Output voltage regulation (Economy line mode)

+/- 10%

Output voltage regulation (Battery mode)

+/- 3%

Built-in UPS output receptacles

4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)

Page 2
Image 2
Tripp Lite SU3000RTXLCD3U instruction manual Specifications, Output