Storage Temperature Range

Relative Humidity

AC mode BTU / hr. (full load)

AC economy mode BTU / hr. (full load)

Battery mode BTU / hr. (full load)

AC mode efficiency rating (100% load)

AC economy mode efficiency rating (100% load)

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

0 to 95%, non-condensing

1767

707

1784

90%

96%

Operating Elevation (ft.)

Audible Noise

Operating Elevation

(m)

COMMUNICATIONS

0-3000m (0 to 10,000 ft.)

60 dBA at front side 1 meter

0-3000 m

Communications interface

Network monitoring port description

PowerAlert software

Communications cable

WatchDog compatibility

USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports

Included

USB, DB9 serial and EPO cables included

Yes

LINE / BATTERY TRANSFER

Transfer time

Low voltage transfer to battery power (setpoint)

No transfer time (0 ms.) in online, double-conversion mode

156V (full load) / 100V (50% load or less, derates linearly)

High voltage transfer to battery power (setpoint)

SPECIAL FEATURES

280V (full load) / 300V (90% load or less)

Cold Start (startup in battery mode during a power failure)

Cold-start operation supported

High availability UPS features

Green & high efficiency features

CERTIFICATIONS

Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module; Hot swappable batteries

High efficiency economy mode operation; Support for daily startup and shutoff; Schedulable daily hours of economy mode operation

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances)

Page 6
Image 6
Tripp Lite SU6000RT4UTF warranty Communications, Line / Battery Transfer, Special Features, Certifications