Recommended | 208/240V AC 50A circuit with either a 50A Hubbell CS8264C female connector or CS8269 wall receptacle |
Electrical Service |
|
|
|
BATTERY |
|
Full load runtime | 6 min. (8000VA/6400W) |
|
|
Half load runtime | 15 min. (4000VA/3200W) |
|
|
Expandable battery | Runtime is expandable with optional external battery packs |
runtime |
|
|
|
Connects to UPS via | Included |
|
|
DC system voltage | 240VDC |
|
|
Typical battery | |
lifespan |
|
|
|
Battery recharge rate | Less than 8 hours to 90% (included battery set only) |
|
|
VOLTAGE REGULATION |
|
Voltage regulation | |
description | nominal voltage at all times |
|
|
Overvoltage | Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within |
correction | 2% of selected nominal |
|
|
Brownout correction | Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC, |
| regulating output within 2% of selected nominal |
|
|
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. LED/LCD display panel easily rotates for viewing in rackmount or tower configurations.
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 331 |
|
|
Shipping weight (kg) | 150.3 |
|
|
Shipping Dimensions | 39.75 x 31.5 x 23 |
(HWD/in) |
|
|
|
Shipping Dimensions | 101 x 80 x 58.4 |
(HWD/cm) |
|
|
|
Unit weight (lbs) | Power Module 55 lbs., Battery Pack: 136.5 lbs. |
|
|
Unit weight (kg) | Power Module 25 kg., Battery Pack: 62 kg |
|
|
Unit Dimensions | Power Module 5.14 x 17.5 x 25, Battery Pack 5.16 x 17.5 x 25 (Installed depth of power module extends to 32.5 inches |
(HWD/in) | once detachable PDU backplate is installed) |
|
|
Unit Dimensions | Power Module 13.3 x 44.4 x 63.5, Battery Pack 13.4 x 40.6 x 63.5 (Installed depth of power module extends to 82.6 cm |
(HWD/cm) | once detachable PDU backplate is installed) |
|
|
Material of | Steel |
construction |
|
|
|
Form factors | Rack (6U) |
supported |
|
|
|
Cooling method | Fan |
|
|
Battery Access | User replaceable, hot swappable external battery pack |
|
|
ENVIRONMENTAL |
|