INSTALLATION PROCEDURES
Carpentry Procedures
Case
The N5D, N5DH, N5DL and N5DSC models have four
See
Electrical Procedures
Electrical Considerations
CAUTION
Make sure all electrical connections at com- ponents and terminal blocks are tight.
NOTE
Since the lower front cladding is shipped loose, the wiring has immediate access.
Case Fan Circuit
This circuit is to be supplied by an uninter- rupted, protected 120V circuit. The case fan circuit is not cycled during defrost on any of these models.
Fluorescent Lamp Circuit
N5D/N5DH/N5DL/N5DSC case lighting is supplied by 800MA HO horizontal lights. It is controlled by a light switch in each case. The standard lighting is
LNDSC cases are
Defrost Information
See
Defrost Control Chart
|
| Defrost |
|
Defrost | Defrosts | Duration | Term. |
Type | Per Day | (Min) | Temp. |
Off Time | 4 | 24 |
WIRING DIAGRAMS
ELECTRICIAN NOTE - OVERCURRENT
PROTECTION
120V circuits should be protected by 15 or 20 Amp devices per the requirements noted on the cabinet nameplate or the National Electrical Code, Canadian Electrical Code - Part 1, Section 28. 208V defrost circuits employ No. 12 AWG field wire leads for field connections. On remote cases intended for end to end
The following wiring diagrams on pages 7 thru 12 will cover the N5D, N5DH, N5DL and N5DSC case circuits and the lighting circuits.