Design ■ Features ■ Performance
CLR2060 MODEL
Low Side Pressure Changes
The chart above shows the low side pressure changes through the cycles of a CLR2060 unit. It shows that during a harvest cycle, the low side pressures climb to nearly 60 psig. When the freeze cycle starts, the pressure quickly drops to approx. 17 psig and throughout the freeze cycle it continues to slowly drop to approximately 7 psig just before the harvest cycle.
This unit was operating in a 75° fahrenheit ambient temperature and the incoming water temperature was 50° fahrenheit.
If a unit is operating in conditions other than these, the low side pressures will be different. A unit operating in a warmer ambient environment or using warmer water will have higher pressure readings. A unit in a cooler ambient environment or using cooler water will have lower pressure readings.
99