United States Stove 1261 PART E - Figure, Does Not Pass Through A Combustible Wall, Part C Figure

Models: 1261

1 12
Download 12 pages 41.08 Kb
Page 8
Image 8
PART B FIGURE 8 -

PART B FIGURE 8 -

(FIGURE 8 CONTINUED)

MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.

 

 

 

FLUE

FACTORY-BUILT

 

 

CHIMNEY

 

 

 

CHIMNEY LENGTH

 

 

 

 

NONSOLUBLE

 

 

 

 

 

 

REFACTORY

 

 

 

CEMENT

 

 

CHIMNEY LENGTH

FLUSH WITH INSIDE

AIR SPACEOF FLUE 9 IN. MINIMUM

MASONRY CHIMNEY CONSTRUCTED

TO NFPA 211

AIR SPACE

MINIMUM CLEARANCE 9 IN. ALL AROUND

CHIMNEY CONNECTOR PART C FIGURE 8 TO HEATER

USE CHIMNEY MFRS. PARTS TO

ATTACH CONNECTOR SECURELY

SOLID INSULATED, LISTED FACTORY-BUILT CHIMNEY LENGTH

SHEET STEEL SUPPORTS

(24 GAUGE MIN. THICKNESS)

PART C FIGURE 8

MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.

TWO VENTILATED AIR CHANNELS EACH 1 INCH. CONSTRUCTED OF SHEET STEEL.

CHIMNEY THIMBLE

CHIMNEY FLUE

MASONRY CHIMNEY CONSTRUCTED TO NFPA 211

24 GAUGE

VENTILATED THIMBLE WITH TWO 1 INCH AIR CHANNELS

CHIMNEY CONNECTOR

TO HEATER

MINIMUM 6 IN. GLASS

FIBER INSULATION ALL AROUND

SHEET STEEL SUPPORTS (24 GAUGE MIN. THICKNESS)

PART D FIGURE 8

MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.

SHEET STEEL SUPPORTS

CHIMNEY SECTION

 

CHIMNEY THIMBLE

CHIMNEY

 

CONNECTOR

FLUE

 

2 IN.

CHIMNEY

AIR SPACE

 

MASONRY CHIMNEY CONSTRUCTED

TO NFPA 211

MINIMUM CLEARANCE 2 IN. ALL AROUND

1 IN. AIR SPACE TO CHIMNEY LENGTH

CHIMNEY CONNECTOR

TO HEATER

SOLID INSULATED, LISTED

FACTORY-BUILT CHIMNEY

LENGTH (12 IN. LONG MIN.)

SHEET STEEL SUPPORTS (24 GAUGE MIN. THICKNESS)

PART E - (Figure 8)

In addition to the methods shown by A, B, C, and D of Figure 8, a listed factory-built wall pass-through system may be purchased and installed according to the instructions packaged with it to provide a safe method of passing chimney connector through a combustible wall for a connection to a masonry chimney.

CONNECTION OF CHIMNEY CONNECTOR TO A MASONRY CHIMNEY WHEN CHIMNEY CONNECTOR

DOES NOT PASS THROUGH A COMBUSTIBLE WALL

If the chimney connector does not have to pass through a combustible wall to get to a masonry chimney, simply connect the chimney connector directly to the masonry chimney's chimney thimble as described and shown by parts C and D of Figure 8. Remember, the chimney connector should extend into the chimney thimble to the innerface of the chimney flue but not beyond; if the chimney connector is extended through the chimney thimble into the chimney flue, resistance to the flow of smoke and gases up the chimney will occur; that flow resistance will have an adverse affect on the operation and performance of the heater and venting system.

8

Page 8
Image 8
United States Stove 1261 PART E - Figure, Does Not Pass Through A Combustible Wall, Part B Figure Continued, Part C Figure

FAQ

What are the minimum chimney clearances for the United States Stove model 1261?

The minimum chimney clearances from masonry to sheet steel supports and combustibles for the United States Stove model 1261 can be found in Parts B, C, and D of Figure 8 in the official manual.

How should the chimney connector be attached securely to the heater?

Use chimney manufacturer's parts to attach the connector securely. For more details, refer to the instructions provided in the official manual.

What should be considered when connecting the chimney connector to a masonry chimney?

The chimney connector should extend into the chimney thimble to the innerface of the chimney flue, but not beyond, to avoid resistance to the flow of smoke and gases up the chimney.

What is the minimum thickness for the sheet steel supports?

The minimum thickness for the sheet steel supports is 24 gauge, as specified in the official manual.