VENT INSTALLATION

VENT INSTALLATION

WARNING: This boiler shall not be connected to any portion of a mechanical

draft system operating under positive pressure.

1.The vent pipe must slope upward from the boiler not less than 1/4 inch for every 1 foot to the vent terminal.

2.Horizontal portions of the venting system shall be supported rigidly every 5 feet and at elbows. No portion of the vent pipe should have dips or sags.

3.This boiler series is classified as a Category 1 appliance and the vent installation shall be in accordance with Part 7 & 11 of the latest revision of the National Fuel Gas Code or applicable provisions of the local building codes.

4.Inspect chimney to make certain it is constructed according to National Board of Fire Underwriters.

5.Attach draft hood to flue collector at rear of boiler, (See figure 7, below), with sheet metal screw(s) through hole(s) provided. The vent or vent collector shall be Type B or metal pipe having resistance to heat and corrosion not less than that of galvanized sheet steel or aluminum not less than 0.016 inch thick (No. 28 GA).

6.Connect flue pipe same as draft hood to chimney. Bolt or screw joints together to avoid sag. Flue pipe should not extend beyond inside wall of chimney. Do not install manual damper in flue pipe or reduce size of flue outlet except as provided by the latest revision of ANSI Z223.1. Protect combustible ceiling and walls near flue pipe with fireproof insulation. Where two or more appliances vent into a common flue, the area of the common flue must be at least equal to the area of the largest flue plus 50 percent of the areas of each additional flue.

 

WARNING:

 

 

 

 

 

 

 

 

 

ALL

 

 

 

 

 

INSTALLATIONS OF BOILERS

 

 

 

 

 

AND VENTING SHOULD BE

 

 

 

 

 

DONE ONLY BY A QUALIFIED

 

 

 

 

 

EXPERT AND IN ACCORDANCE

 

 

 

 

 

WITH THE APPROPRIATE UTICA

 

 

 

 

 

BOILERS MANUAL. INSTALLING

 

 

 

 

 

OR VENTING A BOILER OR ANY

 

 

 

 

 

OTHER GAS APPLIANCE WITH

 

 

 

 

 

IMPROPER METHODS

OR

 

 

 

 

 

MATERIALS MAY RESULT IN

 

 

 

 

 

SERIOUS INJURY OR DEATH

 

 

 

 

 

DUE TO FIRE OR TO

 

 

 

 

 

ASPHYXIATION

FROM

 

 

 

 

 

POISONOUS GASES SUCH AS

 

 

 

 

 

CARBON MONOXIDE WHICH IS

 

 

 

 

 

ODORLESS AND INVISIBLE.

 

 

 