NATURAL GAS RESIDENTIAL HEATERS

TROUBLESHOOTING

Note: For additional help, visit DESA International’s technical service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off and un- plug heater and let cool before servicing. Only a qualified ser- vice person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no

1.

Ignitor electrode positioned wrong

1.

Replace ignitor

spark at ODS/pilot

2.

Ignitor electrode broken

2.

Replace ignitor

 

3.

Ignitor electrode not connected to igni-

3.

Reconnect ignitor cable

 

 

tor cable

 

 

 

4.

Ignitor cable pinched or wet

4.

Free ignitor cable if pinched by any

 

 

 

 

metal or tubing. Keep ignitor cable dry

 

5.

Piezo ignitor nut is loose

5.

Tighten nut holding piezo ignitor to

 

 

 

 

heater cabinet. Nut is located inside

 

 

 

 

heater cabinet at top

 

6.

Broken ignitor cable

6.

Replace ignitor cable

 

7.

Bad piezo ignitor

7.

Replace piezo ignitor

 

 

 

 

 

When ignitor button is pressed, there is

1.

Gas supply turned off or equipment

1.

Turn on gas supply or open equipment

spark at ODS/pilot but no ignition

 

shutoff valve closed

 

shutoff valve

 

2.

Control knob not in PILOT position

2.

Turn control knob to PILOT position

 

3.

Control knob not pressed in while in

3.

Press in control knob while in PILOT

 

 

PILOT position

 

position

 

4.

Air in gas lines when installed

4.

Continue holding down control knob.

 

 

 

 

Repeat igniting operation until air is re-

 

 

 

 

moved

 

5.

ODS/pilot is clogged

5.

Clean ODS/pilot (see Cleaning and

 

 

 

 

Maintenance, page 19) or replace ODS/

 

 

 

 

pilot assembly

 

6.

Gas regulator setting is not correct

6.

Replace gas regulator

 

 

 

 

 

ODS/pilot lights but flame goes out when

1.

Control knob not fully pressed in

1.

Press in control knob fully

control knob is released

2.

Control knob not pressed in long enough

2.

After ODS/pilot lights, keep control

 

 

 

 

knob pressed in 30 seconds

 

3.

Safety interlock system has been triggered

3.

Wait one minute for safety interlock sys-

 

 

 

 

tem to reset. Repeat ignition operation

 

4.

Equipment shutoff valve not fully open

4.

Fully open equipment shutoff valve

 

5.

Thermocouple connection loose at con-

5.

Hand tighten until snug, then tighten 1/4

 

 

trol valve

 

turn more

 

6.

Pilot flame not touching thermocouple,

6.

A) Contact local natural gas company

 

 

which allows thermocouple to cool,

 

 

 

 

causing pilot flame to go out. This prob-

 

B) Clean ODS/pilot (see Cleaning and

 

 

lem could be caused by one or both of

 

Maintenance, page 19) or replace ODS/

 

 

the following:

 

pilot assembly

 

 

A) Low gas pressure

 

 

 

 

B) Dirty or partially clogged ODS/pilot

 

 

 

7.

Thermocouple damaged

7.

Replace thermocouple

 

8.

Control valve damaged

8.

Replace control valve

www.desatech.com

For more information, visit www.desatech.com

16

107101

Page 16
Image 16
Vanguard Heating VMH3000TNSA installation manual Troubleshooting, Observed Problem Possible Cause Remedy

VMH3000TNSA specifications

The Vanguard Heating VMH3000TNSA is a state-of-the-art heating solution designed to provide optimal warmth and comfort in various settings. This model, part of Vanguard's advanced heating line, stands out with its impressive blend of efficiency, technology, and user-friendly features.

One of the key highlights of the VMH3000TNSA is its powerful heating capacity. The unit is capable of delivering up to 3000 watts, making it suitable for larger spaces. This high output ensures that even in the coldest climates, users can enjoy a consistently warm environment. Its ability to rapidly heat up a room is a significant advantage, especially during the winter months.

Efficiency is another crucial feature of the VMH3000TNSA. It incorporates advanced heating technology that maximizes energy consumption. The unit is designed to provide heat with minimal energy use, thus helping to reduce electricity bills while still maintaining a comfortable temperature. This eco-friendly approach is perfect for those who are looking to minimize their environmental footprint without compromising on comfort.

The VMH3000TNSA is equipped with an intelligent digital thermostat that allows for precise temperature control. Users can easily set their desired temperature and let the unit automatically adjust its output to maintain that level. This feature not only enhances convenience but also contributes to energy savings, ensuring that the heater does not overwork itself.

Safety is a paramount concern with any heating device, and the Vanguard VMH3000TNSA does not disappoint. It features a built-in safety shut-off mechanism that automatically turns the unit off if it overheats. Additionally, the design includes cool-touch technology, ensuring that the exterior of the heater remains safe to touch, preventing accidental burns.

The unit is designed for ease of use and portability. It comes with integrated handles and a lightweight construction, allowing users to effortlessly move the heater from one room to another. This flexibility is particularly beneficial for individuals who want to heat specific areas of their home without having to invest in multiple heaters.

In terms of design, the VMH3000TNSA boasts a modern and sleek appearance that fits seamlessly into any home decor. Its compact size means it doesn’t take up much space, making it ideal for apartments and smaller homes.

Overall, the Vanguard Heating VMH3000TNSA is a top-tier heating solution that excels in performance, efficiency, safety, and design. Whether you are looking to heat a large living space or need a reliable unit for your office, the VMH3000TNSA stands as a versatile and effective choice to keep you warm throughout the colder months.