Page 42 Version 1.0 March 1, 2000
P052 = 21
P052 = 0
With DC BUS connected to the
COMMON DC BUS of the system, set
P52=21 and provide a start command
at terminal X101, pin #9
The circuit identification test will take
about 10 seconds.
P052=0 Drive back to ready mode.
Standard Commissioning for a Common
Rectifier or a Regenerative Rectifier
without Autotransformer is complete, after
adjusting only 8 parameters.