Clearance Requirements
Minimum Clearances to
Combustible Materials
Measure side clearances as shown in Figures 2 through 5 from the outer edge of the cast iron stove top. Measure rear clearances from the outermost surface of the sheet metal rear skirt.
The Dutchwest heater is approved for installation into an alcove constructed of combustible materials to the dimensions and clearances shown in Figure 5.
The same clearances apply in a standard parallel instal- lation.
Parallel Installation: Minimum Clearance
and Flue Centerline
C
L
| C |
D | A |
| |
| C |
| L |
B |
|
|
Stove Clearances | A: 5” (125mm) |
|
| B: 4” (102mm) |
|
Pipe Centerlines | C: 16” (406mm) |
|
| D: 9¹⁄₄” (235mm) | ST128c |
Fig. 2 Parallel installation requirements.
Corner Installation: Minimum Clearance and
Flue Centerline
B
A
B
A |
|
|
Stove Clearance | A: 4” (102mm) |
|
Pipe Centerline | B: 17” (432mm) | ST129c |
Fig. 3 Corner installation requirements.
Dutchwest Natural Vent Gas Heater
Ceiling Clearances
45"
(1140mm)
72"
(1829mm)
ST774
Fig. 4 Minimum ceiling clearance; minimum alcove height.
Alcove Minimum Dimensions
C
A | A |
| B |
A: 4” (102mm) | B: 33” (838mm) | C: 5” (125mm) |
|
| ST775 |
Fig. 5 The Dutchwest Natural Vent Stove is approved for installation into alcoves built of combustible materials.
Hearth Requirements
The Dutchwest Heater must be installed on rigid floor- ing. When the heater is installed directly on any com- bustible surface other than wood flooring, a metal or wood panel extending the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.
WARNING:
• Always maintain required clearances (air spaces) to nearby combustibles
to prevent fire hazard. Do not fill air spaces with insulation. All venting compo- nents must maintain a 1” (25 mm) clearance to combustible materials. Maintain a 6” (152 mm) clearance when using single wall pipe.
•The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or
•Refer to the manufacturer’s instructions in- cluded with the venting system for complete installation procedures.