Encore
•The fireplace damper must be sealed to prevent room air from escaping up the flue. However, it must be possible to reopen the damper to inspect or clean the chimney.
Through the Fireplace
If your fireplace opening height is at least 26¹⁄₂" (675mm), you may install an Encore
Fireplace installations, whether connected to the flue above or through the fireplace opening, have special clearance requirements to adjacent trim and the mantel.
Floor protection requirements also apply to fireplace installations. Refer to “Floor Protection” section.
Always adhere to local building codes when installing a wall
All combustible material in the wall must be removed around the
Figure 9 shows another method of passing a connector through a wall. All combustible material in the wall is cut away to provide the required clearance that is 3x the connector diameter. The resulting space must remain empty. A
DO NOT CONNECT AN ENCORE
Flexible Connector
Mantel Shield
Fireplace Adapter
Kit “Positive Con- nection”
ST245
Fig. 8 In this installation, the chimney connector enters the firepalce opening and then connects to the chimney.
Wall Pass-Throughs
Whenever possible, design your installation so the con- nector does not pass through a combustible wall. If you are considering a wall
Also, check with the chimney connector manufacturer for any specific requirements. Some manufacturers make chimney components that may be used as wall
ST494
Fig. 9 A hollow wall
Hearths
This appliance must be installed on to hearth that meets the requirements of Part J of the Building Regu- lations 2000 (Combustion Appliances and Fuel Storage Systems). This can be achieved by ensuring that the hearth is constructed and sized in accordance with the guidelines included in section 2 of approved document ‘J’. The size and clearances of the hearth are as fol- lows:
The constructed hearth should be constructed in ac- cordance with the recommendations in document J, and should be of minimum width 840 mm and minimum depth 840 mm (if a free standing hearth b) above) or a minimum projection of 150 mm from the jamb (if a recessed hearth a) above).
Unless the stove hearth is completely noncombustible, the bottom heat shield should be installed to provide radiant protection for framing which may be below the hearth. (Fig. 11)
8 | 2000971 |