•The
•Supply and return air flow from the evaporator unit shall be unobstructed for at least 1 foot.
•There is a gravity drain line so that it can not be installed above the evaporator unit. Otherwise a condensation pump must be used.
3. Air Sensor
•The air sensor can be located in the wine room or the return air area, but not the supply air area.
4. Refrigeration Piping and Charging
NOTES: ALWAYS USE THE SUPERHEAT AND SUBCOOLING, PRESSURE READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED CHARGES ARE FOR REFERENCE ONLY.
•The installation order starts from condensing unit (including the receiver), liquid line
•The subcooling at the condensing unit shall be around 10°F. The charge may be complete when there are no more bubbles forming in the sight glass.
•If equipped with a TXV, the evaporator superheat is set around
•If equipped with an AXV, the valve is set around
•Low side pressure: 33 psig
•High side pressure: 130 psig at 75 °F ambient temperature and 150 psig at 90 °F ambient temperature
The line sizes and refrigerant charges are listed as follows.
MODEL | REFRIGERATION | LIQUID | SUCTION | |
LINES | LINE | LINE | ||
| ||||
VINO- | < 50 FT | 1/4" | 3/8” OD | |
2500SSD | OD | |||
|
| |||
VINO- | < 50 FT | 1/4" | 1/2” OD | |
4500SSD | OD | |||
|
| |||
VINO- | < 50 FT | 1/4" | 5/8” OD | |
6500SSD | OD | |||
|
| |||
VINO- | < 50 FT | 3/8" | 5/8” OD | |
8500SSD | OD | |||
|
|
DRAIN
LINE
1/2” OD
1/2” OD
1/2” OD
1/2” OD
CHARGE
R134a/
20OZ R134a/
26OZ R134a/
32OZ R134a/
38OZ
- 1 -